When C6-05 is set lower than 7, C6-04 is disabled and the carrier frequency will be fixed to the value set in C6-03.
Note:
ated Current Dependin on Carrier Fre uency
The table below shows the drive output current depending on the carrier frequency settings.
The 2 kHz values shown in
frequency above 2 kHz will reduce the rated output current of the drive as shown in
Model
2A0011
2A0017
2A0024
2A0031
2A0046
2A0059
2A0075
2A0088
2A0114
2A0143
2A0169
2A0211
2A0273
2A0343
2A0396
4A0005
4A0008
4A0011
4A0014
4A0021
4A0027
4A0034
4A0040
4A0052
4A0065
4A0077
4A0096
4A0124
4A0156
4A0180
Carrier Frequency
C6-03
C6-04
Fi ure 1 22 Carrier Fre uency C an es elati e to Output Fre uency
are equal to the drive rated current shown on the drive nameplate. Increasing the carrier
Table 1.13
able 1 1
Carrier Fre uency and Current Deratin
2
10.6
10.6
16.7
16.7
24.2
24.2
30.8
30.8
46.2
46.2
59.4
59.4
74.8
74.8
88
88
114
114
143
143
169
169
211
211
273
273
343
274
396
317
4.8
4.8
7.6
7.6
11
11
14
14
21
21
27
27
34
34
40
40
52
52
65
65
77
77
96
96
124
124
156
156
180
180
Output
Frequency
x C6-05
Output Frequency
E1-04
Max Output Frequency
ated Current (A)
8
ree P ase 2
Class
8.9
14.0
20
26
39
50
63
74
96
114
135
169
218
ree P ase
Class
4.0
6.4
9.2
11.8
17.6
23
29
34
44
55
65
81
99
125
144
Table
1.13.
1
7.8
12.2
17.7
23
34
44
55
65
84
95
113
141
182
3.5
5.6
8.1
10.3
15.4
20
25
29
38
48
57
70
83
104
120
12
6.4
10.0
14.5
18.5
28
36
45
53
68
2.9
4.6
6.6
8.4
12.6
16.2
20
24
31
39
46
58