YASKAWA CIMR-ZU A Series Programming Manual page 122

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1 8 L Protection Functions
No
L8-11
L8 12 Ambient emperature Settin
Automatically adapts the drive rated current to safe values when used with parameter L8-35. This eliminates the need to reduce
the drive rated current when the temperature where the drive is mounted is above the specified values.
No
L8-12
L8 1
oL2 C aracteristics Selection at Lo
Selects whether the drive overload capability (oL fault detection level) is reduced at low speeds to prevent premature output
transistor failures. Set this parameter to 0 (Protection disabled at low speed) when protection is activated for an oL2 fault for
a light load at low speed.
1. Contact Yaskawa before using the drive for applications for which the setting is 0 (disabled).
Note:
2. Do not set this parameter to 0 (disabled) in V/f or OLV control.
3. Do not set this parameter to 0 (disabled) in models 4 0302 to 4 0930.
No
L8-15
Settin
oL2 (Dri e O erload) C aracteristics Disabled at Lo
The overload protection level is not reduced. Frequently operating the drive with high output current at low speed can lead to
premature drive faults.
Settin 1 oL2 (Dri e O erload) C aracteristics Enabled at Lo
The overload protection level (oL2 fault detection level) is automatically reduced at speeds below 6 Hz. At zero speed, the
overload is derated by 50%.
L8 18 So t are Current Limit Selection
Enables and disables the Software Current Limit (CLA) protection function to prevent main circuit transistor failures caused
by high current.
Do not change this setting unless absolutely necessary.
Note:
No
L8-18
Settin
So t are CLA Disabled
The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.
Settin 1 So t are CLA Enabled
When the Software CLA current level is reached, the drive reduces the output voltage to reduce the current. Normal operation
continues when the current level drops below the Software CLA level.
L8 27 O ercurrent Detection Gain
Adjusts the overcurrent detection level in OLV/PM control mode. A setting of 100% is equal to the motor rated current. When
the drive rated current is considerably higher than the motor rated current, use this parameter to decrease the overcurrent level
and prevent motor demagnetization from high current.
Overcurrent detection uses the lower value between the overcurrent level for the drive and the motor rated current multiplied
by L8-27.
No
L8-27
L8 2
Current Unbalance Detection (LF2)
Enables or disables output current unbalance detection in OLV/PM control mode. Current unbalance can heat a PM motor
and demagnetize the magnets. The current unbalance detection function monitors output current and triggers the LF2 fault to
prevent such motor damage.
122
Name
Heatsink Cooling Fan Off-Delay Time
Name
Ambient Temperature Setting
Name
oL2 Characteristics Selection at Low Speed
Name
Software Current Limit Selection
Name
Overcurrent Detection Gain
Settin
Settin
40 to 60 °C
Speeds
Settin
Speed
Speed
Settin
Settin
0.0 to 300.0%
an e
De ault
0 to 300 s
300 s
an e
De ault
40 °C
an e
De ault
0, 1
an e
De ault
Determined by
0, 1
A1-02
an e
De ault
300.0%
1