YASKAWA CIMR-ZU A Series Programming Manual page 158

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1 12
Motor unin
2
PM Motor ated Current
Enter the motor rated current in amps.
No
T2-06
2 7 PM Motor Base Fre uency
Enter the motor base frequency in Hz.
T2-07 will be displayed when in OLV/PM.
Note:
No
T2-07
2 8 Number o PM Motor Poles
Enter the number of motor poles.
No
T2-08
2 1
PM Motor Stator esistance
Enter the motor stator resistance per motor phase.
No
T2-10
2 11 PM Motor d A is Inductance
Enter the d-Axis inductance per motor phase.
No
T2-11
2 12 PM Motor
Enter the q-Axis inductance per motor phase.
No
T2-12
2 1
Induced olta e Constant Unit Selection
Selects the units used for setting the induced voltage coefficient.
No
T2-13
Settin
m (r/min)
Settin 1 m (rad/sec)
If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor Induction
Note:
Voltage Constant 1 (Ke)) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-25 to 0.0.
2 1
PM Motor Induced olta e Constant ( e)
Enter the motor induced voltage constant (Ke).
No
T2-14
1 8
Name
PM Motor Rated Current
Name
PM Motor Base Frequency
Name
Number of PM Motor Poles
Name
PM Motor Stator Resistance
Name
PM Motor d-Axis Inductance
A is Inductance
Name
PM Motor q-Axis Inductance
Name
Induced Voltage Constant Unit Selection
Name
PM Motor Induced Voltage Constant (Ke)
Settin
an e
0.0% to 300.0% of the
Determined by o2-04
drive rated current.
Settin
an e
0.0 to 240.0 Hz
Settin
an e
2 to 48
Settin
an e
0.000 to 65.000 Ω
Determined by T2-02
Settin
an e
0.00 to 600.00 mH
Determined by T2-02
Settin
an e
0.00 to 600.00 mH
Determined by T2-02
Settin
an e
0, 1
Settin
an e
0.0 to 2000.0
Determined by T2-02
De ault
De ault
87.5 Hz
De ault
6
De ault
De ault
De ault
De ault
0
De ault