YASKAWA CIMR-ZU A Series Programming Manual page 84

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1 7
erminal Functions
Settin AC PI2 Inte ral old
Locks the value of the secondary PI controller integral value.
Settin AD Select PI2 Parameters
Uses the secondary PI controller Proportional and Integral adjustments (S3-06 and S3-07) instead of the primary PI controller
Proportional and Integral adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI controller disabled).
This multi-function input has no effect on the secondary PI controller. It is only used for the primary PI controller (b5-
Note:
Settin AE BP Bypass un
Commands a Run in Bypass mode via closing the BP Bypass Relay multi-function output.
Settin AF Emer ency O erride For ard un
Enables Emergency Override Forward Run.
Emergency Override Reference Selection on page 155
Settin B
Emer ency O erride e erse un
Enables Emergency Override Reverse Run.
Emergency Override Reference Selection on page 155
Settin B1 Customer Sa eties
The Customer Safeties multi-function input functionality is identical to Bypass Drive Enable (Setting 70: Drive Enable 2),
except for the following:
• When the input is open, the stopping method is forced to Coast to Stop
• If the input is open when the Run command is present, a "SAFE" alarm is displayed instead of the "dnE" alarm.
Settin B2 BAS Interloc
The BAS Interlock multi-function input is used in a damper interlock circuit to keep the drive from running until the damper
control relay is closed.
• When the input is open, the drive output is shut off (baseblocked).
• The drive will display an "inTLK" message if the input is open and a Run command is present. It will not display "dnE".
• The state of the BAS Interlock multi-function input has no effect on the Emergency Override multi-function inputs
(H1-
= AF, B0). The Emergency Override command will be accepted if the BAS Interlock digital input is open or closed.
2 Multi Function Di ital Outputs
2 1 to 2
The drive has three multi-function output terminals.
H2-02, and H2-03.
No
H2-01
H2-02
H2-03
Settin
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
8
Refer to S6-01: Emergency Override Speed on page 155
Refer to S6-01: Emergency Override Speed on page 155
erminal M1 M2 M M
Parameter Name
Terminal M1-M2 Function Selection (relay)
Terminal M3-M4 Function Selection (relay)
Terminal M5-M6 Function Selection (relay)
able 1 2
Multi Function Di ital Output erminal Settin s
Function
for details.
for details.
and M M Function Selection
lists the functions available for theses terminals using H2-01,
Table 1.29
Pa e
Settin
9
Frequency Reference Source
85
A
Run Command Source
85
B
Torque Detection 1 (N.O.)
86
C
Frequency Reference Loss
86
E
Fault
86
F
Through Mode
87
10
Minor Fault
87
11
Fault Reset Command Active
88
12
Timer Output
88
and
and
Settin
an e
0 to 1B2
0: During Run
0 to 1B2
1: Zero Speed
0 to 1B2
2: Speed Agree 1
Function
).
Refer to S6-02:
Refer to S6-02:
De ault
Pa e
88
88
88
88
88
88
88
89
89