A 8 F Communication Option Parameters

A 8 F Communication Option Parameters
F
F7 Communication Option Card
Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP, Modbus TCP/IP, and LONWORKS
options. F7 parameters are used for the EtherNet/IP and Modbus TCP/IP options.
No
(Addr
Name
e )
F6-01
Communications Error
(3A2)
Operation Selection
External Fault from
F6-02
Comm. Option
(3A3)
Detection Selection
External Fault from
F6-03
Comm. Option
(3A4)
Operation Selection
Torque Reference/
F6-06
Torque Limit Selection
(3A7)
from Comm. Option
Multi-Step Speed
F6-07
Enable/Disable
(3A8)
Selection when NefRef/
ComRef is Selected
F6-08
Reset Communication
(36A)
Parameters
<5>
F6-14
CC-Link bUS Error
(03BB)
Auto Reset
F6-46
BACnet Baud Rate
(02FC)
F7-01
(3E5)
IP Address 1
<6> <7>
<8>
F7-02
(3E6)
IP Address 2
<6> <7>
<8>
F7-03
(3E7)
IP Address 3
<6> <7>
<8>
2
LCD Display
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
Comm Bus Flt Sel
1: Coast to stop.
0: Ramp to Stop
2: Fast Stop. Decelerate to stop using the deceleration time in
1: Coast to Stop
C1-09.
2: Fast-Stop
3: Alarm only.
3: Alarm Only
4: Alarm only. Continue operation using the frequency
4: Alarm (d1-04)
reference set in d1-04.
5: Alarm (C1-02)
5: Alarm only. Decelerate to stop using the deceleration time
in C1-02.
EF0 Detection
0: Always detected.
0: Always Detected
1: Detection during run only.
1: Only During Run
0: Ramp to stop. Decelerate to stop using the deceleration time
EF0 Fault Action
in C1-02.
0: Ramp to Stop
1: Coast to stop.
1: Coast to Stop
2: Fast Stop. Decelerate to stop using the deceleration time in
2: Fast-Stop
C1-09.
3: Alarm Only
3: Alarm only.
Torq Ref/Lmt Sel
OL /PM
OL /PM
0: Disabled
0: Disabled. Torque reference/limit from option board disabled.
1: Enabled
1: Enabled. Torque reference/limit from option board enabled.
0: Multi-step reference disabled (same as F7)
Fref PrioritySel
1: Multi-step reference enabled (same as V7)
0: Net/Com REF
1: MultiStep Speed
0: Communication-related parameters (F6-
Com Prm Init Sel
when the drive is initialized using A1-03.
0: Init Com Prms
1: Reset all communication-related parameters (F6-
1: No Init Com Prms
the drive is initialized using A1-03.
Bus Err Auto Rst
0: Disabled
0: Disabled
1: Enabled
1: Enabled
BAC Baud Rate
0: 1200
0: 1200 bps
1: 2400
1: 2400 bps
2: 4800
2: 4800 bps
3: 9600
3: 9600 bps
4: 19200
4: 19.2 kbps
5: 38400
5: 38.4 kbps
6: 57600
6: 57.6 kbps
7: 76800
7: 76.8 kbps
8: 115200
8: 115.2 kbps
IP Address 1
Sets the most significant octet of network static IP address.
Sets the second most significant octet of network static IP
IP Address 2
address.
IP Address 3
Sets the third most significant octet of network static IP address.
Description
<1>
<1> <2>
<3> <4>
<1>
<3>
<3>
<3>
alues
Default: 1
Range: 0 to 5
Default: 0
Range: 0, 1
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
) are not reset
Default: 0
) when
Range: 0, 1
Default: 0
Range: 0, 1
Default: 3
Range: 0 to 8
Default: 192
Min.: 0
Max.: 255
Default: 168
Min.: 0
Max.: 255
Default: 1
Min.: 0
Max.: 255
Pa e
72
72
72
72
73
73
73
73