YASKAWA CIMR-ZU A Series Programming Manual page 237

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1
Function
Settin
B1
Customer Safeties
B2
BAS Interlock
2 Multi Function Di ital Outputs
No
(Addr
Name
e )
Terminal M1-M2
H2-01
function selection
(40B)
(relay)
Terminal M3-M4
H2-02
function selection
(40C)
(relay)
Terminal M5-M6
H2-03
function selection
(40D)
(relay)
2
Function
Settin
0
During run
1
Zero speed
2
Speed agree 1
3
User-set speed agree 1
4
Frequency detection 1
5
Frequency detection 2
6
Drive ready
7
DC bus undervoltage
8
During baseblock (N.O.) BaseBlk 1
Frequency reference
9
source
A
Run command source
Torque detection 1
B
(N.O.)
C
Frequency reference loss Loss of Ref
E
Fault
F
Through mode
1 Multi Function Di ital Input Selections
LCD Display
The functionality is identical to Drive Enable 2 (H1-
following characteristics:
• The stopping method is forced to Coast to Stop when the input is open
• The drive will display a "SAFE" alarm if the input is open when a Run command
CustomerSafeties
is present. It will not display "dnE".
Open: Customer Safeties are open. Drive will not run. Stopping method is Coast
to Stop.
Closed: Customer Safeties are in place.
Open: Damper interlock is not closed. Drive output is shut off (baseblocked). The
drive displays an "inTLK" message if a Run command is present. It will not display
"dnE".
Closed: Damper interlock is closed. Drive operates normally.
BAS Interlock
Note:
LCD Display
Refer to H2 Multi-Function Digital Output Settings on pages
M1-M2 Func Sel
to
237
239
M3/M4 Func Sel
M5/M6 Func Sel
2 Multi Function Di ital Output Settin s
LCD Display
During RUN 1
Closed: A Run command is active or voltage is output.
Open: Output frequency is above the minimum output frequency set in E1-09.
Zero Speed
Closed: Output frequency is below the minimum output frequency set in E1-09.
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
Fref/Fout Agree1
set to L4-02).
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
Fref/Set Agree 1
hysteresis set to L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
Freq Detect 1
determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01 with
Freq Detect 2
hysteresis determined by L4-02.
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Drive has entered the baseblock state (no output voltage).
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
Ref Source
b1-15).
Closed: HOA keypad supplies the frequency reference.
Open: External Reference 1 or 2 supplies the Run command (set in b1-02).
Run Cmd Source
Closed: HOA keypad supplies the Run command.
Closed: An overtorque or undertorque situation has been detected.
Trq Det 1 N.O.
Closed: Analog frequency reference has been lost.
Fault
Closed: Fault occurred.
Not Used
Set this value when using the terminal in the pass-through mode.
A
Parameters Multi Function erminals
Description
The state of the BAS Interlock multi-function input has no effect on
the Emergency Override multi-function inputs (H1-
The Emergency Override command is accepted when the BAS
Interlock digital input is open or closed.
Description
for descriptions of setting values.
Description
Pa e
= 70), except for the
84
84
= AF, B0).
alues
Pa e
Default: 0
84
Range: 0 to 1B2
Default: 1
84
Range: 0 to 1B2
Default: 2
84
Range: 0 to 1B2
Pa e
85
85
86
86
86
87
87
88
88
88
88
88
88
88
88
2 7