A 7 E Motor Parameters
<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is dependent on parameters A1-02, Control Model Selection and o2-04, Drive Model Selection.
<4> Default setting is dependent on parameter o2-04, Drive Model Selection.
<5> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<6> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.

E2 Motor Parameters

No
(Addr
Name
e )
E2-01
Motor Rated Current
(30E)
E2-02
Motor Rated Slip
(30F)
E2-03
Motor No-Load Current No-Load Current
(310)
E2-04
Number of Motor Poles Number of Poles
(311)
E2-05
Motor Line-to-Line
(312)
Resistance
E2-10
Motor Iron Loss for
(317)
Torque Compensation
E2-11
Motor Rated Power
(318)
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for
a maximum applicable motor capacity up to and including 11 kW, 2A0031, 4A0021 (input voltage 460 V or higher) or 4A0027 (input voltage lower
than 460 V) and one decimal place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW, 2A0046, 4A0027 (input voltage 460
V or higher) or 4A0034 (input voltage lower than 460 V) .
E
PM Motor Settin s
No
(Addr
Name
e )
E5-02
(32A)
Motor Rated Power
<1>
E5-03
(32B)
Motor Rated Current
<1>
E5-04
(32C)
Number of Motor Poles PM Motor Poles
<1>
228
LCD Display
Sets the motor nameplate full load current in amps.
Automatically set during Auto-Tuning.
Motor Rated FLA
Sets the motor rated slip. Automatically set during
Auto-Tuning.
Motor Rated Slip
Sets the no-load current for the motor. Automatically set during
Auto-Tuning.
Sets the number of motor poles. Automatically set during
Auto-Tuning.
Sets the phase-to-phase motor resistance. Automatically set
during Auto-Tuning.
Term Resistance
Sets the motor iron loss.
Motor Iron Loss
Sets the motor rated power in kilowatts (1 HP = 0.746 kW).
Automatically set during Auto-Tuning.
Mtr Rated Power
LCD Display
OL /PM
OL /PM
PM Mtr Capacity
Sets the rated capacity of the motor.
OL /PM
OL /PM
Sets the motor rated current.
PM Mtr Rated FLA
OL /PM
OL /PM
Sets the number of motor poles.
Description
Description
alues
Pa e
Default:
<1>
Min.: 10% of
drive rated
current
68
Max.: 200% of
drive rated
current
<2>
Default:
<1>
Min.: 0.00 Hz
68
Max.: 20.00 Hz
Default:
<1>
Min.: 0 A
69
Max.: E2-01
<2>
Default: 4
Min.: 2
69
Max.: 48
Default:
<1>
Min.: 0.000 Ω
69
Max.: 65.000 Ω
Default:
<1>
Min.: 0 W
69
Max.: 65535 W
Default:
<1>
Min.: 0.00 kW
69
Max.: 370.00 kW
alues
Pa e
Default:
<2>
Min.: 0.10 kW
70
Max.: 370.00 kW
Default:
<2>
Min: 10% of
drive rated
current
70
Max: 200% of
drive rated
current
<3>
Default:
<2>
Min.: 2
70
Max.: 48