YASKAWA CIMR-ZU A Series Programming Manual page 19

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Settin
Open Loop ector Control or PM
Use this mode when running a PM motor in variable torque applications that benefit from energy efficiency. The drive can
control an SPM or IPM motor with a speed range of 1:20 in this control mode.
A1
Initiali e Parameters
Resets parameters to default values. After initialization, the setting for A1-03 automatically returns to 0.
No
A1-03
Settin
No Initiali e
Settin 111
User Initiali e
Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to
"1: Set defaults".
User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to
Note:
clear the user-defined default values.
Settin 222
2
ire Initiali ation
Resets parameters except parameters listed in
run and Reverse run, respectively.
for more information on digital input functions.
page 80
Settin
ire Initiali ation
Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse
respectively.
Refer to Setting 0: 3-Wire Sequence on page 75
Settin
1
AC Initiali ation
Resets parameters to default settings. The following parameters are not reset:
H1-03: b1 (Customer Safeties)
H1-04: b2 (BAS Interlock)
H1-05: AF (Emergency Override Forward Run)
H2-03: b2 (BAS Interlock Relay Contact)
After performing an HVAC Initialization, H1-03 to H1-05 and H2-03 will be displayed in the Modified Parameters list.
Note:
Settin
2
OEM Bypass Initiali ation
Resets parameters to default settings. The following parameters are not reset:
H1-03: A7 (BP Customer Safeties)
H1-04: A6 (BP BAS Interlock)
H1-05: A4 (Emergency Override)
H1-06: AE (BP Bypass Run)
H2-01: A4 (BP Drive Relay)
H2-02: A5 (BP Bypass Relay)
H2-03: A6 (BP BAS Interlock)
o1-16: 2 (Drive/Bypass)
After performing an OEM Bypass Initialization, H1-03 to H1-05, H2-01 to H2-03, and o1-16 will be displayed in the Modified Parameters
Note:
list.
Notes on Parameter Initiali ation
The parameters shown in
Table 1.1
the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.
Parameter Name
Initialize Parameters
to default settings with digital inputs S1 and S2 configured as Forward
Table 1.1
Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence on
will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. Although
Settin
0, 1110, 2220,
3330, 3410, 3420
for more information on digital input functions.
1 1 A Initiali ation
an e
De ault
0
1
1