YASKAWA CIMR-ZU A Series Programming Manual page 242

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A
Parameters Multi Function erminals
No
(Addr
Name
e )
Communications
H5-11
ENTER Function
(43C)
Selection
H5-12
Run Command Method
(43D)
Selection
H5-14
BAC Dev Obj ID 0
(310D)
H5-15
BAC Dev Obj ID 1
(310E)
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
2 2
LCD Display
0: Drive requires an Enter command before accepting any
Enter CommandSel
changes to parameter settings.
0: Enter Required
1: Parameter changes are activated immediately without the
1: No EnterRequired
Enter command (same as V7).
Run CommandSel
0: FWD/Stop, REV/Stop
0: FWD Run &REV
1: Run/Stop, FWD/REV
Run
1: Run & FWD/REV
BACnet device object ID
BAC Dev Obj Id 0
BACnet device object ID
BAC Dev Obj Id 1
Description
alues
Pa e
Default: 0
290
Range: 0, 1
Default: 0
290
Range: 0, 1
Default: 1
290
Range: 0 to FFFF
Default: 0
290
Range: 0 to 3F