Metasys N2 Binary Input (Bi) Summary - YASKAWA CIMR-ZU A Series Programming Manual

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Metasys N2 Analo Output (AO) Summary
Ob ect ID
Ob ect Name
AO 1
Speed Command
AO 2
Acceleration Time
AO 3
Deceleration Time
AO 4
PI Proportional Gain
AO 5
PI Integral Time
AO 6
Stall Prevention Level – Run
AO 7
Stall Prevention Level – Accel
AO 8
Reference Operation Mode Select
AO 9
Run Operation Mode Select
AO 10
PI Mode Select
AO 11
Frequency Command Upper Limit
AO 12
Frequency Command Lower Limit
AO 13
Motor Rated Current
AO 14
Jump Frequency 1
AO 15
Jump Frequency 2
AO 16
Jump Frequency 3
AO 17
Jump Frequency Bandwidth
AO 18
Number of Auto Restarts
AO 19
Operator Display Mode
AO 20
Power Loss Ride-Thru
AO 21
Cable Loss Timeout
AO 22
Cable Loss Speed
AO 23
PI Integral Limit
AO 24
PI Upper Limit Value
AO 25
PI Offset Adjustment
AO 26
PI Primary Delay Time
PI Feedback Reference Missing
AO 27
Detection Select
PI Feedback Reference Missing
AO 28
Detection Level
PI Feedback Reference Missing
AO 29
Detection Time
AO 30
Read Parameter Number
AO 31
Write Parameter Number
AO 32
Write Parameter Data

Metasys N2 Binary Input (BI) Summary

Ob ect ID
Ob ect Name
BI 1
Run/Stop Monitor
BI 2
Forward/Reverse Monitor
BI 3
Drive Ready Monitor
BI 4
Fault Monitor
BI 5
Zero Speed
BI 6
Speed Agree
BI 7
Minor Fault
BI 8
Major Fault
BI 9
Drive Communication Error Monitor
able D
Metasys N2 Analo Output Summary ( 1
Units
0.01 Hz
seconds
seconds
seconds
%
%
% of Max
% of Max
A
0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz
seconds
seconds
0.01 Hz
0.1%
0.1
0.1
0.01
1
1%
0.1 s
able D
Metasys N2 Binary Input Summary ( 1
De ault
0
Stopped
0
Forward
0
Not Ready
0
Not Faulted
0
Not Zero Speed
0
Not Speed Agree
0
No Minor Fault
0
No Major Fault
0
No Error
D 7 Metasys N2 Point Database
to Metasys N2)
De ault alue
30.0
30.0
2.00
5.0
120
120
1
1
0
100.0
0.0
Motor model dependent
0.0
0.0
0.0
1.0
0
0
Drive model dependent
2.0
0.00
100.0
100.0
0.0
0.00
0
0
1.0
to Metasys N2)
O ( ) State
Running
Reverse
Ready
Faulted
Zero Speed
Speed Agree
Minor Fault
Major Fault
Error
1
Parameter
C1-01
C1-02
b5-02
b5-03
L3-06
L3-02
b1-01
b1-02
b5-01
d2-01
d2-02
E2-01
d3-01
d3-02
d3-03
d3-04
L5-01
o1-03
L2-02
H5-09
d1-04
b5-04
b5-06
b5-07
b5-08
b5-12
b5-13
b5-14
On (1) State