YASKAWA CIMR-ZU A Series Programming Manual page 34

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1 2 b Application
This mode requires that the Power Loss Ride-Thru function is enabled during CPU operation (L2-01 = 1 or 2).
Momentary Power Loss Operation Selection on page
Method 5. After external baseblock is released.
The drive will resume the operation starting with Speed Search if the Run command is present and the output frequency is
above the minimum frequency when the Baseblock command (H1-
b
1 Speed Searc Selection at Start
Determines if Speed Search is automatically performed when a Run command is issued.
No
b3-01
Settin
Disabled
This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed
Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Settin 1 Enabled
This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search
is complete.
b
2 Speed Searc Deacti ation Current
Sets the operating current for Speed Search as a percentage of the drive rated current. Normally there is no need to change
this setting. Lower this value if the drive has trouble restarting.
No
b3-02
When parameter A1-02 = 0 (V/f Control) the factory default setting is 120.
Note:
b
Speed Searc Deceleration ime
Sets the output frequency reduction ramp used by the Current Injection Method of Speed Estimation (b3-24 = 1). The time
entered into b3-03 will be the time to decelerate from maximum frequency (E1-04) to minimum frequency (E1-09).
No
b3-03
b
/ Gain durin Speed Searc (Speed Estimation ype)
During Speed Search, the output voltage calculated from the V/f pattern is multiplied with this value. Changing this value can
help reduce the output current during Speed Search.
No
b3-04
b
Speed Searc Delay ime
In cases where an output contactor is used between the drive and the motor, the contactor must be closed before Speed Search
can be performed. This parameter can be used to delay the Speed Search operation, giving the contactor enough time to close
completely.
No
b3-05
104.
Parameter Name
Speed Search Selection at Start
Name
Speed Search Deactivation Current
Name
Speed Search Deceleration Time
Name
V/f Gain during Speed Search
Name
Speed Search Delay Time
= 8 or 9) is released.
Settin
an e
0, 1
Settin
an e
0 to 200%
Settin
an e
0.1 to 10.0 s
Settin
an e
10 to 100%
Settin
an e
0.0 to 100.0 s
Refer to L2-01:
De ault
Determined by
A1-02
De ault
Determined by
A1-02
De ault
2.0 s
De ault
Determined by
o2-04
De ault
0.2 s