YASKAWA CIMR-ZU A Series Programming Manual page 239

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

2
Function
Settin
BP Bypass Relay
A5
Contact
BP BAS Interlock Relay
A6
Contact
A9
Relay Operator Control PI2 Disable N.C.
BAS Interlock Relay
B2
Contact
Function 0 to b2 with
inverse output
Note: A prefix of "!" is
100 to
added to represent
1B2
inverse functions on the
LCD keypad display.
Example: "!Zero speed"
Multi Function Analo Inputs
No
(Addr
Name
e )
H3-01
Terminal A1 Signal
(410)
Level Selection
H3-02
Terminal A1 Function
(434)
Selection
H3-03
Terminal A1 Gain
(411)
Setting
H3-04
Terminal A1 Bias
(412)
Setting
H3-09
Terminal A2 Signal
(417)
Level Selection
H3-10
Terminal A2 Function
(418)
Selection
H3-11
Terminal A2 Gain
(419)
Setting
H3-12
Terminal A2 Bias
(41A)
Setting
H3-13
Analog Input Filter Time
(41B)
Constant
H3-14
Analog Input Terminal
(41C)
Enable Selection
H3-16
Terminal A1 Offset
(2F0)
2 Multi Function Di ital Output Settin s
LCD Display
Closed: Line voltage is being supplied directly to the motor.
BP Drv/Bypss Sel
Closed: Actuation signal for options dampers.
BP BAS Interlock
Closed: F1 (F2) key toggle relay output.
BAS Interlock
A Run command is active or voltage is output. Actuation signal for damper.
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1
LCD Display
0: 0 to 10 V with zero limit
Term A1 Level
1: 0 to 10 V without zero limit
0: 0-10V,
2: 4-20 mA
(LowLim=0)
3: 0-20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A1.
Term A1 FuncSel
Sets the level of the input value selected in H3-02 when 10 V
is input at terminal A1.
Terminal A1 Gain
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Terminal A1 Bias
0: 0 to 10 V with zero limit
Term A2 Level
1: 0 to 10 V without zero limit
0: 0-10V,
2: 4 to 20 mA
(LowLim=0)
3: 0 to 20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A2.
Term A2 FuncSel
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Terminal A2 Bias
Sets a primary delay filter time constant for terminals A1 and
A1/A2 Filter T
A2. Used for noise filtering.
Determines which analog input terminals will be enabled when
A1/A2 Sel
a digital input programmed for "Analog input enable"
1: A1 Available
(H1-
2: A2 Available
1: Terminal A1 only
3: A1/A2 Available
2: Terminal A2 only
3: Terminals A1 and A2
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
Term A1 Offset
A
Parameters Multi Function erminals
Description
to reverse the output signal of that specific function.
Description
Use jumper switch S1 to set input terminal A1
for current or voltage.
Use jumper switch S1 to set input terminal A2
for current or voltage input signal.
= C) is activated.
Pa e
93
93
93
93
93
alues
Pa e
Default: 0
94
Range: 0 to 3
Default: 0
94
Range: 0 to 26
Default: 100.0%
Min.: -999.9
94
Max.: 999.9
Default: 0.0%
Min.: -999.9
94
Max.: 999.9
Default: 2
95
Range: 0 to 3
Default: 0
95
Range: 0 to 26
Default: 100.0%
Min.: -999.9
96
Max.: 999.9
Default: 0.0%
Min.: -999.9
96
Max.: 999.9
Default: 0.03 s
Min.: 0.00
96
Max.: 2.00
A
Default: 2
96
Range: 1 to 3
Min.: -500
97
Max.: 500
2