YASKAWA CIMR-ZU A Series Programming Manual page 91

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Frequency
Detection 4
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 112
Settin 1B Durin Basebloc (N C )
The output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not switch
and no main circuit voltage is output.
Status
Open
Baseblock is being executed.
Closed
Drive is not in a baseblock state.
Settin 1E
estart Enabled
An output set for "Restart enabled" closes when the drive attempts to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has attempted to restart. If the drive cannot successfully restart within the number of attempts permitted
by L5-01, a fault will be triggered and the terminal set to 1E will open.
automatic restart.
Settin 1F Motor O erload Alarm (oL1)
The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level.
Refer to L1-01: Motor Overload Protection Selection on page
Settin 2
Dri e O er eat Pre Alarm (o )
The output closes when the drive heatsink temperature reaches the level specified by parameter L8-02 or an external device
has triggered an oH2 alarm via mult-function digital input H1-
for details on drive overheat detection.
119
Settin 2F Maintenance Period
The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined
by the estimated performance life span of those components. Components performance life is displayed as a percentage on
the HOA keypad screen.
Settin
7 Durin Fre uency Output
The output closes when the drive is outputting a frequency.
Status
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed
Drive is outputting frequency.
Output Frequency
OFF
ON
Fi ure 1 8 Fre uency Detection
L4-04
L4-03
E ample
it Positi e L
Description
Refer to L5: Fault Restart on page 113
101.
= B.
Refer to L8-02: Overheat Alarm Level on page
Description
1 7
erminal Functions
alue
for more details.
for details on
1
1