When an input terminal programmed for 42 closes, the drive will operate in the selected direction. The drive will stop when
the input opens.
The input programmed for 43 selects the direction. If the input is open, forward direction is selected. If the input is closed,
reverse direction is selected.
This function cannot be used simultaneously with settings 40 and 41.
Note:
Settin s
and
O set Fre uency 1 2
These inputs add offset frequencies d7-01, d7-02, and d7-03 to the frequency reference.
Frequency 1 to 3 on page 63
Settin
7 Node Setup
If the SI-S3 option card is connected, closing this terminal sets a node address for operation on a CANopen network.
Settin s
and A GF1 Error (N O N C )
These input functions will stop the drive when a GF1 error is detected when set together with F6-86 (GF1 Error Detection
Selection) and F6-87 (GF1 Error Operation Selection).
Settin
Motor Pre
eat 2
Sets the DC preheat current as a percentage of motor rated current (E2-01).
details.
81
Settin
1 Se uence imer Disable
Drive ignores sequence timers and runs normally (based on b1-02/b1-16 source).
Settin
2 Se uence imer Cancel
The sequence timers are canceled.
Settin
Motor Pre
eat 1
A DC current can be circulated through the motor windings to create heat and prevent moisture from condensing on the wire.
Motor Pre-Heating can only be initiated by closing a digital input programmed as a Motor Pre-Heat input (H1-
level of the DC current used by the Motor Pre-Heat function is determined by b2-09.
A Run input will be given priority over a Motor Pre-Heat input and when the Run command is removed, the motor pre-heating
will resume if the Motor Pre-Heat input is still closed.
Settin
1
2 E ternal Speed Searc Command 1 2
These input functions enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start).
for details on how to use the input signals.
Activation on page 33
Search.
Simultaneously assigning Speed Search 1 and Speed Search 2 to the input terminals will trigger an oPE03 error.
Note:
Settin
Field
ea enin
Enabled in V/f Control. When this input is closed, Field Weakening is performed.
for details.
OFF
Motor Pre-Heat 1
command
OFF
FWD Run command
Motor Pre-Heat 1
Output frequency
Fi ure 1 8 Motor Pre
Refer to Setting 60: Motor Pre-Heat 1 on page
ON
OFF
ON
Motor Pre-Heat 1
braking
Motor Pre-Heat 1
Start Frequency
(b2-01)
eat 1 Input imin Dia ram
Refer to b3: Speed Search on page 31
1 7
erminal Functions
Refer to d7-01 to d7-03: Offset
= 60). The
OFF
Refer to Speed Search
for more about Speed
1
81