YASKAWA CIMR-ZU A Series Programming Manual page 71

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

No
E5-05
E
Motor d A is Inductance (Ld)
Sets the d-Axis inductance in 0.01 mH units.
No
E5-06
E
7 Motor
A is Inductance (L )
Sets the q-Axis inductance in 0.01 mH units.
No
E5-07
E
Motor Induction olta e Constant 1 ( e)
Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an IPM
motor with variable torque.
No
E5-09
Set E5-24 to 0 when setting E5-09. However, setting both E5-09 and E5-24 to 0 will trigger an alarm. An alarm will also be triggered if
Note:
neither E5-09 nor E5-24 are set to 0.
E 2
Motor Induction olta e Constant 2 ( e)
Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using an
SPM Motor.
No
E5-24
Set E5-24 to 0.0 when setting E5-09. However, setting both E5-09 and E5-24 to 0.0 will trigger an alarm. An alarm will also be triggered
Note:
if neither E5-09 nor E5-24 are set to 0.0.
Parameter Name
Motor Stator Resistance
Parameter Name
Motor d-Axis Inductance
Parameter Name
Motor q-Axis Inductance
Parameter Name
Motor Induction Voltage Constant 1
Parameter Name
Motor Induction Voltage Constant 2
1
E Motor Parameters
Settin
an e
0.000 to 65.000 Ω
Settin
an e
0.00 to 300.00 mH
Settin
an e
0.00 to 600.00 mH
Settin
an e
0.0 to 2000.0 mV/(rad/s)
Settin
an e
0.0 to 6500.0 mV/(r/min)
De ault
Determined by
o2-04
De ault
Determined by
o2-04
De ault
Determined by
o2-04
De ault
Determined by
o2-04
De ault
Determined by
o2-04
1
71