A2 User Parameters - YASKAWA CIMR-ZU A Series Programming Manual

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A
A Initiali ation Parameters
A
A Initiali ation Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
A1 Initiali ation
No
(Addr
Name
e )
A1-00
(100)
Language Selection
<1>
A1-01
(101)
Access Level Selection
<2>
A1-02
Control Method
(102)
Selection
<1>
A1-03
Initialize Parameters
(103)
A1-04
Password
(104)
A1-05
Password Setting
(105)
A1-06
Application Preset
(127)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.

A2 User Parameters

No
(Addr
Name
e )
A2-01 to
A2-32
User Parameters 1 to
(106 to
32
125)
A2-33
User Parameter
(126)
Automatic Selection
<1> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<2> Default setting value is dependent on parameter A1-06. Default is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0.
21
LCD Display
Select Language
0: English
0: English
1: Japanese
1:
(Japanese)
3: French
3: Fran ais
5: Spanish
5: Español
6: Portuguese
6: Portuguêse
0: View and set A1-01 and A1-04.
Access Level
U -
0: Operation Only
1: User Parameters (access to a set of parameters selected by the
1: User Parameters
user, A2-01 to A2-32)
2: Advanced Level
2: Advanced Access (access to view and set all parameters)
0: V/f Control
Control Method
5: Open Loop Vector Control for PM
0: V/F Control
5: PM OpenLoop Vect
Init Parameters
0: No initialization
0: No Initialize
1110: User Initialize (parameter values must be stored using
1110: User Initialize
parameter o2-03)
2220: 2-Wire Initial
2220: 2-Wire Initialization
3330: 3-Wire Initial
3330: 3-Wire Initialization
3410: SELVAL
3410: HVAC Initialization
HVAC Initialize
3420: OEM Bypass Initialization
3420: SELVAL OEM
Bypass Init
Enter Password
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03, A1-06, and A2-01
through A2-33 cannot be changed.
Select Password
Application Sel
0: Standard
0: General
1: Fan
1: Fan General
2: Fan with PI Control
2: Fan PI
3: Return Fan with PI Control
3: Fan ReturnAir/PI
4: Cooling Tower Fan
4: Cooling Tower
5: Cooling Tower Fan with PI Control
5: CoolingTower/PI
6: Pump (Secondary)
6: Pump Secondary
7: Pump with PI Control
7: Pump PI
LCD Display
Recently edited parameters are listed here. The user can also
select parameters to appear here for quicker access.
User Param 1 - 32
0: Parameters A2-01 to A2-32 are reserved for the user to create
User Parms Sel
a list of User Parameters.
0: Disabled
1: Save history of recently viewed parameters.
1: Enabled
Recently edited parameters will be saved to A2-17 through
A2-32 for quicker access.
Description
parameters can also be viewed.
Description
alues
Pa e
Default: 0
18
Range: 0 to 6
Default: 2
18
Range: 0 to 2
Default: 0
18
Range: 0, 5
Default: 0
19
Range: 0 to 3420
Default: 0000
Min.: 0000
20
Max.: 9999
Default: 0000
Min.: 0000
20
Max.: 9999
Default: 0
22
Range: 0 to 7
alues
Pa e
Default:
<1>
Range: A1-00 to
22
S6-07
Default: 1
<2>
23
Range: 0, 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000