YASKAWA CIMR-ZU A Series Programming Manual page 259

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

No
(Addr
Name
e )
S3-16
Secondary PI High
(3229)
Feedback Detection
Time
S3-17
(322A) Secondary PI Feedback
Detection Selection
<1> Unit is determined by S3-04.
<2> Upper limit is S3-02, decimal placeholder is determined by S3-03.
S
Bypass Operation
No
(Addr
Name
e )
S4-01
(322B) BP Auto Transfer on
Fault Enable
S4-02
(322C) BP Energy Save Bypass
Trigger Level
S4-03
(322D) BP Energy Save Bypass
Timer
S4-04
BP Energy Save Bypass
(322E)
Speed Increase
S
OA eypad Parameters
No
(Addr
Name
e )
S5-01
HAND Frequency
(322F)
Reference Selection
S5-02
HAND/AUTO During
(3230)
Run Selection
S5-03
HAND Mode PI
(3231)
Selection
S5-04
HAND Mode Behavior
(3232)
Selection
S5-05
HAND Frequency
(3233)
Reference 1
LCD Display
Sets the secondary PI high feedback detection delay time in
seconds.
PI2 High FB Tim
0: Secondary PI enabled
PI2 FB Det Sel
1: Always
0: PI2 Enabled
1: Always
LCD Display
0: No transfer after fault
BP Fault Trnsfer
1: Transfer to bypass after fault
0: Disabled
1: Enabled
Delta used to determine when to switch into Energy Save Bypass.
BP Enrgy Sav Lvl
This allows for lower frequency output values to also trigger
Energy Save Bypass functionality.
Sets the time in seconds that the drive should run at the specified
speed before entering Energy Save Bypass mode.
BP Enrgy Sav TMR
Sets the value in Hz that the drive will increase the output
frequency above E1-04 before performing an Energy Save
BP Enrgy Sav Inc
transfer to bypass.
LCD Display
HAND Fref Source
0: HOA keypad
0: Operator
1: Terminals
1: Terminals
2: d1-16
2: d1-16
3: S5-05
3: S5-05
4: Determined by b1-01
4: Set by b1-01
HAND/AUTO
0: Disabled
@Run
1: Enabled
0: Disabled
1: Enabled
0: Disabled
HAND Mode PI Sel
1: Enabled
0: Disabled
1: Enabled
0: Legacy operation mode
1: Normal operation mode
HAND BehaviorSel
2: Normal with memory
0: Legacy
Note:
1: Normal
2: Normal w/
Memory
Sets the frequency reference used in HAND mode when S5-01 is
set to 3.
HAND Freq Ref 2
Description
Description
Description
1. The drive will always be in AUTO mode at
power up with S5-04 = 1.
2. When S5-04 = 2, if the drive is powered down
with HAND from the HOA keypad, the drive
will power up in OFF mode.
A 1 S Special Application
alues
Pa e
Default: 1.0 s
Min.: 0.0
Max.: 25.5
Default: 0
Range: 0, 1
alues
Pa e
Default: 1
Range: 0, 1
Default: 0 Hz
Min.: 0
Max.: 20
Default: 60 s
Min.: 10
Max.: 60000
Default: 6 Hz
Min.: 0
Max.: 10
alues
Pa e
Default: 0
Range: 0 to 4
Default: 1
Range: 0, 1
Default: 1
Range: 0, 1
Default: 1
Range: 0 to 2
Default: 0.00
Hz
Min.: 0.00
Max.: [E4-01]
<1>
145
145
151
151
152
152
152
152
152
152
A
154
2

Advertisement

Table of Contents