YASKAWA CIMR-ZU A Series Programming Manual page 353

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

ritin to Multiple e isters
Function code 10H allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process
works similar to reading registers, in that the address of the first register to be written and the data quantity are set in the
command message. The data to be written must be consecutive so that the register addresses are in order, starting from the
specified address in the command message. The data order must be high byte then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference of
60.00 Hz for the slave 1 drive.
If parameter values are changed using the Write command, an Enter command may be necessary to activate or save the data
depending on the setting of H5-11.
Enter Command on page 300
Command Messa e
Slave Address
Function Code
Upper
Starting No.
Lower
Upper
Data Quantity
Lower
Number of Bytes
Upper
Starting Data
Lower
Upper
Next Data
Lower
Upper
CRC-16
Lower
Double the number of the data quantity for the number of bytes in the command message.
Note:
Refer to H5-11: Communications Enter Function Selection on page 290
for detailed descriptions.
esponse Messa e (normal)
01H
Slave Address
10H
Function Code
00H
Upper
Starting No.
01H
Lower
00H
Upper
Data Quantity
02H
Lower
04H
Upper
CRC-16
00H
Lower
01H
17H
70H
63H
39H
esponse Messa e ( ault)
01H
Slave Address
10H
Function Code
00H
Error Code
01H
CRC-16
00H
02H
10H
08H
E 8 Messa e E amples
and
Refer to
01H
90H
02H
Upper
CDH
Lower
C1H
E