YASKAWA CIMR-ZU A Series Programming Manual page 88

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1 7
erminal Functions
Settin 7 DC Bus Under olta e
The output closes when the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A fault in
the DC bus circuit will also cause the terminal set for "DC bus undervoltage" to close.
Status
Open
DC bus voltage is above the level set to L2-05.
Closed
DC bus voltage has fallen below the trip level set to L2-05.
Settin 8 Durin Basebloc (N O )
The output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Settin
Fre uency e erence Source
Displays the currently selected frequency reference source.
Status
Open
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15).
Closed
Frequency reference is being sourced from the HOA keypad.
Settin A
un Command Source
Displays the currently selected Run command source.
Status
Open
Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Closed
Run command is being sourced from the HOA keypad.
Settin B and 17
or ue Detection 1 (N O N C )
These digital output functions signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below.
for details.
116
Settin
Status
B
Closed
17
Open
Settin C Fre uency e erence Loss
An output set for this function closes when frequency reference loss is detected.
Detection Selection on page 113
Settin E Fault
The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Settin F
rou
Mode
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function in
the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or MEMOBUS/
Modbus communications.
Settin 1
Minor Fault
The output closes when a minor fault condition is present.
88
Torque detection 1 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 1 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
for details.
Description
Description
Description
Description
Refer to L6: Torque Detection on page
Description
Refer to L4-05: Frequency Reference Loss