YASKAWA CIMR-ZU A Series Programming Manual page 238

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A
Parameters Multi Function erminals
2
Function
Settin
10
Minor fault
Fault reset command
11
active
12
Timer output
13
Speed agree 2
14
User-set speed agree 2
15
Frequency detection 3
16
Frequency detection 4
Torque detection 1
17
(N.C.)
1A
During Reverse
1B
During baseblock (N.C.) BaseBlk 2
1E
Restart enabled
Motor overload alarm
1F
(oL1)
Drive overheat pre-
20
alarm (oH)
2F
Maintenance period
37
During frequency output During RUN 2
38
Drive enabled
39
Watt hour pulse output
3A
Drive overheat alarm
3D
During speed search
3E
PI feedback low
3F
PI feedback high
4A
During KEB Ride-Thru During KEB
During short circuit
4B
braking
4C
During fast stop
4D
oH Pre-alarm time limit OH Pre-Alarm
50
Waiting for run
51
Sequence timer 1 active SeqTimer Disable
52
Sequence timer 2 active SeqTimer Cancel
53
Sequence timer 3 active Sequence timer 3
54
Sequence timer 4 active Sequence Timer 4
58
Underload detection
Internal cooling fan
60
alarm
Secondary PI Feedback
71
Low
Secondary PI Feedback
72
High
A4
BP Drive Relay Contact BP Emg Override
2 8
2 Multi Function Di ital Output Settin s
LCD Display
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their
Minor Fault
expected life span.
Closed: A command has been entered to clear a fault via the input terminals or
Reset Cmd Active
from the serial network.
Timer Output
Closed: Timer output.
Fref/Fout Agree2
Closed: When drive output frequency equals the frequency reference ±L4-04.
Fref/Set Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.
Closed: When the drive output frequency is less than or equal to the value in L4-03
Freq Detect 3
±L4-04.
Closed: When the output frequency is greater than or equal to the value in L4-03
Freq Detect 4
±L4-04.
Open: Overtorque or undertorque has been detected.
Trq Det 1 N.C.
Reverse Dir
Closed: Drive is running in the reverse direction.
Open: Drive has entered the baseblock state (no output voltage).
Dur Flt Restart
Closed: An automatic restart is performed
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers
Overload (OL1)
this alarm.
Closed: Heatsink temperature exceeds the L8-02 Overheat Alarm Level, or an
OH Prealarm
external device has triggered an oH2 alarm via multi-function digital input H1-
= B.
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
Maintenance
may require maintenance.
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is
not being performed).
Drive Enable
Closed: Multi-function input set for "Drive enable" is closed (H1-
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
Watt-hour Pulse
the kWh count.
OH Alarm 2
Closed: Heatsink temperature exceeds the L8-02 Overheat Alarm Level.
During SpdSrch
Closed: Speed Search is being executed.
PI Feedback Low
Closed: PI feedback level is too low.
PI FeedbackHigh
Closed: The PI feedback level is too high.
Closed: KEB Ride-Thru is being performed.
OL /PM
OL /PM
During SC Brake
Closed: Short Circuit Braking is active.
Closed: A Fast Stop command has been entered from the operator or input
During Fast Stop
terminals.
Closed: oH pre-alarm time limit has passed.
Waiting for Run
Closed: Delay executing any run command until the time set to b1-11 has expired.
Closed: Sequence timer 1 is active.
Closed: Sequence timer 2 is active.
Closed: Sequence timer 3 is active.
Closed: Sequence timer 4 is active.
UL6
Closed: Underload is detected.
Closed: Internal cooling fan alarm
Fan Alrm Det
Closed: PI2 feedback level is too low.
PI2 Feedback Low
Closed: The PI2 feedback level is too high.
PI2 FeedbackHigh
Closed: Line voltage is being supplied to the drive, and the motor is being run via
the drive.
Description
Pa e
88
89
89
89
89
90
90
88
88
91
91
91
91
91
91
= 6A)
92
92
92
92
92
92
92
92
92
92
92
92
92
92
92
92
93
93
93
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000

Table of Contents