Status
Open
Output frequency or motor speed exceeded L4-01 + L4-02.
Closed
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Note:
Frequency
detection 1
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 112
Settin
Fre uency Detection 2
The output closes when the output frequency or motor speed is above the detection level set in L4-01. The terminal remains
closed until the output frequency or motor speed fall below L4-01 minus the setting of L4-02.
Status
Open
Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed
Output frequency or motor speed exceeded L4-01.
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Note:
Frequency
Detection 2
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 112
Settin
Dri e eady
The output closes when the drive is ready to operate the motor. The terminal will not close under the conditions listed below,
and any Run commands will be disregarded.
• When the power is shut off
• During a fault
• When the internal power supply of the drive has malfunctioned
• When a parameter setting error makes it impossible to run
• Although stopped, an overvoltage or undervoltage situation occurs
• While editing a parameter in the Programming Mode (when b1-08 = 0)
Output Frequency
OFF
ON
Fi ure 1
Fre uency Detection 1 ime C art
Output Frequency
OFF
ON
Fi ure 1
Fre uency Detection 2 ime C art
Description
L4-02
L4-01
Description
L4-02
L4-01
1 7
erminal Functions
L4-01
L4-02
for more details.
L4-01
L4-02
for more details.
1
87