YASKAWA CIMR-ZU A Series Programming Manual page 268

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A 1 U Monitors
No
(Addr
Name
e )
U4-18
Frequency Reference
(7DA)
Source Selection
Frequency Reference
U4-19
from MEMOBUS/
(7DB)
Modbus Comm.
U4-20
Option Frequency
(7DC)
Reference
U4-21
Run Command Source
(7DD)
Selection
MEMOBUS/Modbus
U4-22
Communications
(7DE)
Reference
U4-23
Communication Option
(7DF)
Card Reference
<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
U
PI Monitors
No
(Addr
Name
e )
U5-01
PI Feedback
(0057)
U5-02
PI Input
(0063)
U5-03
PI Output
(0064)
U5-04
PI Setpoint
(0065)
U5-05
PI Differential Feedback PI Feedback 2
(07D2)
2 8
LCD Display
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
0 = OFF
1 = AUTO
2 = HAND
Y-nn: indicates the reference source
0-01 = HOA keypad
Reference Source
1-00 = Analog (not assigned)
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
9-01 = Up/Down
Displays the frequency reference provided by MEMOBUS/
MEMOBUS Freq Ref
Modbus (decimal).
Displays the frequency reference input by an option card
Option Freq Ref
(decimal).
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
0 = OFF
1 = AUTO
2 = HAND
Y: Input power supply data
0 = HOA keypad
1 = External terminals
3 = Serial communications (APOGEE FLN, BACnet,
MEMOBUS/Modbus, or Metasys N2)
4 = Communication option card
nn: Run command limit status data
Run Cmd Source
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to
REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv
or Uv1 flashes after 10 s)
04: Waiting for "Run command prohibited" time period to end
05: Fast Stop (digital input, HOA keypad)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during
baseblock
09: Waiting for Enter command
Displays the drive control data set by MEMOBUS/Modbus
MEMOBUS Ref Reg
communications register no. 0001H as a four-digit hexadecimal
number.
Displays drive control data set by an option card as a four-digit
Option Ref Reg
hexadecimal number.
LCD Display
Displays the PI feedback value.
PI Feedback 1
Displays the amount of PI input (deviation between PI setpoint
PI Input
and feedback).
Displays PI control output.
PI Output
Displays the PI setpoint.
PI Setpoint
Displays the second PI feedback value if differential feedback is
used (H3-
Description
Description
= 16).
Analo
Unit
Output Le el
No signal output
available
No signal output
0.01%
available
No signal output
available
No signal output
available
No signal output
available
No signal output
available
Analo
Unit
Output Le el
10 V: 100%
<1>
10 V: 100%
0.01%
10 V: 100%
0.01%
10 V: 100%
<1>
10 V: 100%
0.01%