Settin 11 Fault eset Command Acti e
The output closes when there is an attempt to reset a fault situation from the control circuit terminals, via serial communications,
or using a communications option card.
Settin 12
imer Output
This setting configures a digital output terminal as the output for the timer function.
for details.
37
Settin 1
Speed A ree 2 (
The output closes when the actual output frequency or motor speed is within the speed agree width (L4-04) of the current
frequency reference, regardless of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-04.
Detection works in forward and reverse.
Note:
Output Frequency
Speed Agree 2
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 112
Settin 1
User Set Speed A ree 2 (
The output closes when the actual output frequency or motor speed and the frequency reference are within the speed agree
width (L4-04) of the programmed speed agree level (L4-03).
Status
Open
Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04.
Closed
Output frequency or motor speed and the frequency reference are both within the range of L4-03 ±L4-04.
The detection level L4-03 is a signed value; detection works in the specified direction only.
Note:
/
A ree 2)
re
out
Frequency
reference
or Motor Speed
OFF
ON
Fi ure 1
/
A ree 2)
re
set
Description
L4-04
Speed A ree 2 ime C art
Description
1 7
erminal Functions
Refer to b4: Timer Function on page
L4-04
for more details.
1
8