YASKAWA CIMR-ZU A Series Programming Manual page 25

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Current Input
Input terminals A1 and A2 can accept a current input signal. Refer to
able 1
Si nal
erminal
Le el
4 to 20 mA
A1
0 to 20 mA
4 to 20 mA
A2
0 to 20 mA
Fi ure 1 2 Settin t e Fre uency e erence as a Current Si nal to erminal A2
S itc in bet een Main/Au iliary Fre uency e erences
The frequency reference input can be switched between the analog terminals A1 and A2 using multi-speed inputs.
Multi-Step Speed Selection on page 58
Settin 2 Serial Communication (APOGEE FLN BACnet MEMOBUS/Modbus Metasys N2)
This setting requires entering the frequency reference via the RS-422/RS-485 serial communications port (control terminals
R+, R-, S+, and S-).
Refer to MEMOBUS/Modbus Configuration on page 340
Settin
Option Card
This setting requires entering the frequency reference via an option board plugged into connector CN5 on the drive control
board. Consult the option card manual for instructions on integrating the drive with the communication system.
If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Programming Error will
Note:
be displayed on the HOA keypad and the drive will not run.
b1 2
un Command Selection or AU O Mode
Determines the Run command selection for AUTO mode.
No
b1-02
Settin 1 Control Circuit erminal
This setting requires entering the Run command via the digital input terminals using one of following sequences:
• 2-Wire sequence 1:
Two inputs (FWD/Stop-REV/Stop). Set A1-03 to 2220 to initialize the drive and preset terminals S1 and S2 to these
functions. This is the default setting of the drive.
Wire Sequence on page
• 2-Wire sequence 2:
Two inputs (Start/Stop-FWD/REV).
page
80.
• 3-Wire sequence:
Analo Input Settin s or Fre uency e erence Usin a Current Si nal
Parameter Settin s
Si nal Le el
Function
Selection
Selection
H3-01 = 2
H3-02 = 0
(Frequency
H3-01 = 3
Reference Bias)
H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-09 = 3
Jumper S1
Terminal A1/A2
Voltage/Current
Selection
V
I
A1 A2
0 or 4 to 20 mA
for details on using this function.
Parameter Name
Run Command Selection for AUTO Mode
Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-
80.
Refer to Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2 on
to set terminals A1 and A2 for current input.
Table 1.6
Gain
H3-03
H3-11
Drive
V
I
A1 A2
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
AC Analog input common
for instructions.
1 2 b Application
Notes
Bias
H3-04
Make sure to set Jumper S1 on the
terminal board to "I" for current
input.
H3-12
Settin
an e
1 to 3
Refer to
De ault
1
1
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000