YASKAWA CIMR-ZU A Series Programming Manual page 151

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Fwd Run
Bypass Run
Drive Enable-Customer
Safeties
Override (Smoke Purge)
Drive/Bypass Select
BAS Interlock
BP Drive Relay Contact
Output
BP Bypass Relay Contact
Output
BP BAS Interlock Contact
Output
SFS Output Frequency
S
1 BP Auto rans er on Fault Enable
Enables Auto-Transfer when a fault occurs.
No
S4-01
Settin
No rans er a ter Fault
Settin 1
rans er to Bypass a ter Fault
S
2 BP Ener y Sa e Bypass ri
Delta used to determine when to switch into Energy Save Bypass. This allows for lower frequency output values to also trigger
Energy Save Bypass functionality. A transfer to bypass occurs after the drive reaches the programmed output frequency (E1-04
to S4-02) for the time specified in the BP Energy Save Bypass Timer (S4-03). Additionally, if frequency input is set below
E1-04 to S4-02, the drive exits Energy Save Bypass. Setting S4-02 to 0 disables Energy Save Bypass functionality.
BP Energy Save
Bypass Timer
Fi ure 1 81 Ener y Sa in s Mode
Name
BP Auto Transfer on Fault Enable
er Le el
Speed
Search
<2>
Occurs
<1>
L2-03
S4-03
Frequency Commanded to less than
E1-04 minus S4-02 (BP Energy Save
Bypass Trigger Level)
Settin
1 11 S Special Parameters
L2-03
an e
De ault
0 or 1
0
1
1 1