YASKAWA CIMR-ZU A Series Programming Manual page 240

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A
Parameters Multi Function erminals
No
(Addr
Name
e )
H3-17
Terminal A2 Offset
(2F1)
Function
Settin
0
Frequency bias
1
Frequency gain
Auxiliary frequency
reference 1
2
(used as a Multi-Step
Speed 2)
Auxiliary frequency
3
reference 2
(3rd step analog)
4
Output voltage bias
5
Accel/decel time gain
DC Injection Braking
6
current
Overtorque/undertorque
7
detection level
Stall Prevention level
8
during run
Output frequency lower
9
limit level
B
PI feedback
C
PI setpoint
D
Frequency bias
Motor temperature (PTC
E
input)
F
Through mode
16
Differential PI feedback PI Feedback 2
25
Secondary PI Setpoint
26
Secondary PI Feedback PI2 Feedback
Analo Outputs
No
(Addr
Name
e )
Multi-Function Analog
H4-01
Output Terminal FM
(41D)
Monitor Selection
H4-02
Multi-Function Analog
(41E)
Output Terminal FM
Gain
H4-03
Multi-Function Analog
(41F)
Output Terminal FM
Bias
Multi-Function Analog
H4-04
Output Terminal AM
(420)
Monitor Selection
2
LCD Display
Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0
Term A2 Offset
Multi Function Analo Input Settin s
LCD Display
Freq Ref Bias
10 V = E1-04 (maximum output frequency)
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
Freq Ref Gain
of -100 to 0%.
10 V = E1-04 (maximum output frequency)
Aux Reference1
10 V = E1-04 (maximum output frequency)
Aux Reference2
Voltage Bias
10 V = E1-05 (motor rated voltage)
Acc/Dec Change
10 V = 100%
10 V = Drive rated current
DC Brake Current
10 V = Drive rated current (V/f)
Torque Det Level
10 V = Motor rated torque (OLV/PM)
10 V = Drive rated current
Stall Prev Level
10 V = E1-04 (maximum output frequency)
Ref Lower Limit
PI Feedback1
10 V = 100%
PI Set Point
10 V = 100%
Freq Ref Bias 2
10 V = E1-04 (maximum output frequency)
10 V = 100%
Motor PTC
Not Used
Set this value when using the terminal in the pass-through mode.
10 V = 100%
PI2 Setpoint
10 V = S3-02 (maximum output frequency)
10 V = S3-02 (maximum output frequency)
LCD Display
Selects the data to be output through multi-function analog
output terminal FM.
Term FM FuncSel
Set the desired monitor parameter to the digits available in
U -
For example, enter "103" for U1-03.
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.
Terminal FM Bias
Selects the data to be output through multi-function analog
output terminal AM.
Terminal AM Sel
Set the desired monitor parameter to the digits available in
U -
For example, enter "103" for U1-03.
Description
Description
Description
.
.
alues
Pa e
Min.: -500
97
Max.: 500
Pa e
97
97
97
97
97
97
97
98
98
98
98
98
98
98
98
98
98
98
alues
Pa e
Default: 102
Range: 000 to
98
655
Default: 100.0%
Min.: -999.9
99
Max.: 999.9
Default: 0.0%
Min.: -999.9
99
Max.: 999.9
Default: 103
Range: 000 to
98
655