A 1 S Special Application
No
(Addr
Name
e )
S2-06
Sequence Timer 2 Start
(320B)
Time
S2-07
Sequence Timer 2 Stop
(320C)
Time
S2-08
Sequence Timer 2 Day
(320D)
Selection
S2-09
Sequence Timer 2
(320E)
Selection
S2-10
Sequence Timer 2
(320F)
Reference Source
S2-11
Sequence Timer 3 Start
(3210)
Time
S2-12
Sequence Timer 3 Stop
(3211)
Time
S2-13
Sequence Timer 3 Day
(3212)
Selection
S2-14
Sequence Timer 3
(3213)
Selection
2
LCD Display
Sets the start time for timer 2. The value must be set less than or
Tmr 2 Start Time
equal to S2-07.
Sets the stop time for timer 2. The value must be set greater than
Tmr 2 Stop Time
or equal to S2-06.
Tmr 2 Day Sel
Sets the days for which sequence timer 2 is active.
0: Timer disabled
0: Timer disabled
1: Daily
1: Daily
2: Mon - Fri
2: Mon - Fri
3: Sat - Sun
3: Sat - Sun
4: Monday
4: Monday
5: Tuesday
5: Tuesday
6: Wednesday
6: Wednesday
7: Thursday
7: Thursday
8: Friday
8: Friday
9: Saturday
9: Saturday
10: Sunday
10: Sunday
Tmr 2 Seq Sel
Sets the action that occurs when sequence timers 2 is active.
0: Digital out only
0: Digital output only
1: Run
1: Run
2: Run - PI Disable
2: Run - PI disable
Selects the frequency reference source used for running the drive
when sequence timer 2 is active (only applicable when S2-09 is
set to 1 or 2).
Tmr 2 Ref Source
0: Operator (d1-01)
0: Operator (d1-01)
1: Operator (d1-02)
1: Operator (d1-02)
2: Operator (d1-03)
2: Operator (d1-03)
3: Operator (d1-04)
3: Operator (d1-04)
4: Terminals
4: Terminals
5: Serial communication
5: Serial com
6: Option card
6: Option PCB
Note:
Sets the start time for timer 3. The value must be set less than or
Tmr 3 Start Time
equal to S2-12.
Sets the stop time for timer 3. The value must be set greater than
Tmr 3 Stop Time
or equal to S2-11.
Tmr 3 Day Sel
Sets the days for which sequence timer 3 is active.
0: Timer disabled
0: Timer disabled
1: Daily
1: Daily
2: Mon - Fri
2: Mon - Fri
3: Sat - Sun
3: Sat - Sun
4: Monday
4: Monday
5: Tuesday
5: Tuesday
6: Wednesday
6: Wednesday
7: Thursday
7: Thursday
8: Friday
8: Friday
9: Saturday
9: Saturday
10: Sunday
10: Sunday
Tmr 3 Seq Sel
Sets the action that occurs when sequence timer 3 is active.
0: Digital out only
0: Digital output only
1: Run
1: Run
2: Run - PI Disable
2: Run - PI disable
Description
H1-
= 12/13 overrides this sequence run timer
in drive software versions PRG: 1018 and later.
alues
Pa e
Default: 00:00
Min.: 00:00
140
Max.: 24:00
Default: 00:00
Min.: 00:00
140
Max.: 24:00
Default: 0
141
Range: 0 to 10
Default: 0
141
Range: 0 to 2
Default: 0
141
Range: 0 to 6
Default: 00:00
Min.: 00:00
140
Max.: 24:00
Default: 00:00
Min.: 00:00
140
Max.: 24:00
Default: 0
141
Range: 0 to 10
Default: 0
141
Range: 0 to 2