1) Performance Specifications
Name
Model Name
Model No.
Rated Voltage
Maximum Allowable Voltage
Rated Frequency
Allowable Frequency Range
Inrush Current
Rated Current
Input Impedance
Standard Operating Ranges
Input Type
Input Delay Times
Number of common
Number of Inputs per Common
Input Power Supply per Common
External Connections
Number of Inputs
Input Signal Indication
Status Indication
Insulation Method
Dielectric Strength
Insulation Resistance
External Power Supply
Derating Conditions
Internal Current Consumption
This section describes the performance specifications, circuit configuration, external
connections, and the external appearance of the 120-series Digital Input Modules.

3.1.1 100-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-2

3.1.2 200-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-6
3.1.3 12/24-VDC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-10
3.1.4 12/24-VDC 32-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-14
3.1.5 12/24-VDC 64-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-18
100-VAC 16-point Input Module
Item
100-VAC 16-point Input Module
AC100IN-16P
JAMSC-120DAI54300
100 VAC
132 VAC
50/60 Hz
47 to 63 Hz
160 mA
7 mA (at 100 VAC, 50 Hz)
14.3 kΩ (at 100 VAC, 50 Hz)
12.5 kΩ (at 100 VAC, 50 Hz)
ON voltage range: 74 to 132 VAC
OFF voltage range: 30 VAC max.
AC type2 (according to JIS B3502)
OFF to ON: 20 ms max.
ON to OFF: 35 ms max.
2
8 points/common
Connect power supplies of the same phase to the Common 1 and
Common 2.
Removable terminal block with M3 screw terminals
16
Indicator for each point; lit when the input is ON.
Status saved in internal logic.
ACTIVE: Lights during input processing
Photocoupler
1,500 VAC for 1 min or 1,800 VAC for 1 s between input terminals and
internal circuits and between all input commons.
100 MΩ min. at room temperature and humidity between input termi-
nals and ground
(measured with a 500-VDC test voltage megohmmeter).
100 VAC supplied to signals
None
90 mA max. at 5 VDC (with all points ON)
Specifications
3-2