(7) Prohibition of Installation of Phase Advancing Capacitor
Do not connect a phase advancing capacitor or surge absorber to main circuit power supply input (R/L1, S/L2,
or T/L3) of a power regeneration converter. The phase advancing capacitor or surge absorber may become
overheated and damaged by the harmonic components of the Σ-V-SD driver. Also, the Σ-V-SD driver may
malfunction because of overcurrent.
(8) Designing the Power ON Sequence
Take the following points into consideration when designing the power ON sequence.
• The main circuit power supply must turn ON only after it has been confirmed that no servo alarm has
occurred.
• The main circuit power supply must turn OFF when a servo alarm occurs during operation. The state of the
motor must be considered when the main circuit power supply is turned OFF during operation. For details,
refer to 7.2.1 (9) Typical Main Circuit Wiring Example.
(9) Typical Main Circuit Wiring Example
The typical main circuit wiring examples is shown below.
• Do not touch the power terminals before the main-circuit capacitor has had time to discharge because
high voltage may still remain in the converter and SERVOPACK. Refer to this section for the details of dis-
charge time of main-circuit capacitor.
After the charge indicator goes out, check the voltage on the DC bus line (i.e., between the P and N terminals) with a
voltage tester or other device and confirm safety before you perform wiring or inspection work.
R S T
1QF
4SA
Main power
supply ON
Emergency
+24 V
stop
0 V
1QF: Molded-case circuit breaker
1FIL: Noise filter
1KM: Magnetic contactor
(for control power supply)
2KM: Magnetic contactor
(for main circuit power supply)
A host controller is not provided by Yaskawa.
WARNING
1FLT
AC Reactor
2KM
U
V
W
1KM
Control
+
power supply
24 VDC
For servo alarm
1Ry
display
1PL
Main power
supply OFF
1KM
1KM
1SA
2KM
1Ry
1KM
3KM
2SA
Host controller
3KM
ESP+
ALM+
3SA
ESP-
ALM-
3KM: Magnetic contactor
(for emergency stop)
1Ry: Relay
1PL: Indicator lamp
1SA: Surge absorber
CACR-JU
CACP-JU
3
SERVOPACK
Converter
X
L1
Y
P
P
L2
N
N
Z
L3
CN7A
24 V
0 V
CN7B
+24 V
1Ry
1D
0 V
2SA: Surge absorber
3SA: Surge absorber
4SA: Surge absorber
1D: Flywheel diode
7.2 Σ-V-SD Driver
CA
P
N
CN7A
CN7B
7
7-23