Omron FH series User Manual page 378

Hide thumbs Also See for FH series:
Table of Contents

Advertisement

Getting Layout Number
Gets the number of the currently displayed layout.
Command (PLC to Sensor Controller)
First word in
Command
Command Area
code
+2
4000
+3
0020
+4
-
+5
-
IMPORTANT
• For non-remote operation, only 0: Local can be specified. For remote operation, only 1: Remote can be specified.
If any combination other than the above combinations is used, unexpected operation may occur when the command is
executed.
Response (Sensor Controller to PLC)
First word in
Command
Response Area
code
+2
4000
+3
0020
+4
-
+5
-
+6
-
+7
-
Getting Display Image Unit Number
Gets the number of the unit currently displayed in the specified image display window.
Command (PLC to Sensor Controller)
First word in
Command
Command Area
code
+2
5010
+3
0020
+4
-
+5
-
376
Command Control
Bit
12 to 15
8 to 11
4 to 7
0100
0000
0000
0000
0000
0010
0000
0000
0000
0000
0000
0000
Bit
12 to 15
8 to 11
4 to 7
0100
0000
0000
0000
0000
0010
0000
0000
0000
0000
0000
0000
0000
0000
0000
0000
0000
0000
Bit
12 to 15
8 to 11
4 to 7
0101
0000
0001
0000
0000
0010
0000
0000
0000
0000
0000
0000
0 to 3
0000
Command code
0000
0000
Item to acquire
0: Local
0000
1: Remote
0 to 3
0000
Command code
Response target command codes
0000
0000
Response code
Command execution result
OK: 0(0000 0000)
0000
NG: Not 0 (0000 0000)
0000
Response data
Current layout number (0 to 8)
0000
0 to 3
0000
Command code
0000
0000
Image display window number
FH: Image display window number (0 to 23)
FZ5:
Displaying 1 image: 1
0000
Displaying 2 images: 1 and 2
Displaying 4 images: 1 to 4
Displaying thumbnails: 0 to 4