Omron FH series User Manual page 110

Hide thumbs Also See for FH series:
Table of Contents

Advertisement

Event name
PLC Link Communications Error
Meaning
A PLC Link cannot be established.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
EtherCAT NET RUN
Indicators
Variable
System-defined
variables
None
Assumed cause
There is a mistake in the PLC or Vision
Cause and
Sensor communications settings.
correction
The Ethernet or RS-232C cable is
damaged.
Attached
None
information
Precautions/
You can download the PLC Link Connection Guide from your OMRON website.
Remarks
Event name
Light installation error
Meaning
The Light installation is incorrect.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
EtherCAT NET RUN
Indicators
Variable
System-defined
variables
None
Assumed cause
The power consumption of the light
installed onto a camera with a Lighting
Controller is incorrect.
Cause and
The lighting mode of the light installed
correction
onto a camera with a Lighting Control-
ler is incorrect.
No external power supply is connected
to the camera with a Lighting Control-
ler.
Attached
None
information
Precautions/
None
Remarks
108
EtherCAT Connections (FH-1000 series/FH-3000 series only)
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
Correction
Correct the communications settings in
the PLC or Vision Sensor.
Replace the Ethernet or RS-232C
cable with a new one.
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
Correction
Install a light whose power consump-
tion is appropriate for the camera with
a Lighting Controller.
Set an appropriate lighting mode for
the light installed onto a camera with a
Lighting Controller.
Connect an external power supply to
the camera with a Lighting Controller.
Event code
8808 0000 hex
Slave
Detection timing
Error reset (after
resetting the error
Log category
in the slave)
You cannot control the Vision Sensor with the PLC Link.
EtherCAT LINK/ACT
---
Name
---
Prevention
Correct the communications settings in
the PLC or Vision Sensor.
Use a flexible cable or take other mea-
sures to prevent the Ethernet or RS-
232C cable from becoming broken.
Event code
385B0000 hex
Slave
Detection timing
Error reset (after
resetting the error
Log category
in the slave)
The light does not turn on.
EtherCAT LINK/ACT
---
Name
---
Prevention
Consult the instruction manual for the
light and confirm that its power con-
sumption is appropriate for the camera
with a Lighting Controller.
Consult the FH/FZ5 Series Vision Sys-
tem Processing Item Function Refer-
ence Manual (Cat. No. Z341-E1), and
confirm the appropriate lighting mode
for the installed light.
Confirm that the cable of an external
power supply is connected.
Vision System FH/FZ5 Series User's Manual
for Communications Settings (Z342)
Always at startup
System
---
---
After turning ON
slave power
System
---
---

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fz5 series

Table of Contents