Note
• When the input command is not received correctly, the ERROR signal turns ON.
• Acquisition is difficult because the amount of time during which the BUSY signal is OFF during a continuous
measurement for a parallel command is extremely short (1 ms or less). Get the OR signal when the GATE signal
turns ON after adding the parallel judgement output at the end of the flow.
Scene/Scene Group Switch
Scenes and scene groups are changed as follows.
When the number of the desired scene or scene group is set in DI0 to DI6 and DI7 is turned ON, the scene or
scene group changes to that set in DI0 to DI6.
• Time Charts
FH
DI0 to DI6 signals
ON
DI7 signal
OFF
ON
ON
BUSY signal
OFF
OFF
ON
READY signal
OFF
ON
ACK signal
OFF
FZ5
DI0 to DI6 signals
ON
DI7 signal
OFF
ON
ON
BUSY signal
OFF
OFF
ON
READY signal
OFF
Vision System FH/FZ5 Series User's Manual
for Communications Settings (Z342)
0
0100001 (to switch to scene 1)
After at
least 1 ms,
IN7 is
Command Request
turned ON.
0
0100001 (to switch to scene 1)
The signal is turned OFF
when the BUSY signal turns ON.
Allow at
least 1 ms
and then
Command Request
turn ON IN7.
The PLC (user) turns OFF the
signal again when the ACK
signal is turned ON.
The signal turns OFF
when DI7 turns OFF.
Timeout [s]
Parallel Communications
2
341