3.1.7

Technical data

Table 2 Technical data of the PM340, FSB (380 V ... 480 V 3 AC ±10 %)
PM340
PM340 with integrated line filter
Output current
Rated current In
Base-load current IH
for S6 operation (40 %) Is6
Peak current Imax
Type rating¹)
on basis of In
on basis of IH
Rated pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1m)
24 V DC supply
for the Control Unit
Rated input current²)
with/without integrated line reactor
Class J UL fuses
Rated current
Short-circuit current rating SCCR
NH fuses IEC 60947
Rated current
Circuit breaker type designation IEC
60947
Rated current
Resistance value
ext. braking resistor
Max. cable length
to braking resistor
Line supply connection
L1, L2, L3
Motor connection
U2, V2, W2
DC link connection, connection for
braking resistor
DCP/R1, DCN, R2
PE connection
Max. motor cable length ³)
shielded/unshielded
Degree of protection
Weight
¹) Rated power of a typical standard induction motor at 400 V 3 AC
²) The input current depends on the motor load and line impedance. The input currents apply for a load with
the type rating (based on I
³) Max. motor cable length 25 m (shielded) for PM340 Power Modules with integrated line filter to maintain
the limit values of EN 61800-3 Category C2.
Siemens S120_EN_rev06-08062017.docx
6SL3210-
6SL3210-
A
A
A
A
kW
kW
kHz
kW
m³/s
dB
A
A
A
kA
A
A
Ω
m
m
kg
) for a line impedance corresponding to uk = 1%.
rated
1SE21-0UA0
1SE21-0AA0
10.2
9.1
10.8
20.4
4
4
4
0.18
0.009
<50
1.0
9.8/12.4
15
65
3NA3803
16
3RV2021-4BA10
14 ... 20
> 160
15
Screw terminals for
cable cross-sections 1.0 ... 6 mm²
On housing with M5 screw
50/75
IP20 or IPXXB
4.0
3-11