Technical Data, Pm240-2; General Data, Pm240-2 - 200 V - Siemens sinamics G120 Operating Instructions Manual

Low voltage inverters chassis devices with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for sinamics G120:
Table of Contents

Advertisement

10.2.1

Technical data, PM240-2

Typical inverter load cycles
Image 10-2
10.2.1.1

General data, PM240-2 - 200 V

Property
Line voltage
Output voltage
Input frequency
Output frequency
Line impedance
Power factor λ
Inrush current
Overvoltage category acc.
to EN 60664-1
Pulse frequency
Converter with CU250S-2 Control Unit
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
"Low Overload" and "High Overload" load cycles
Version
FSA ... FSC
200 V ... 240 V 1-ph. AC
± 10 %
200 V ... 240 V 3-ph. AC
± 10 %
FSD ... FSF
200 V ... 240 V 3-ph. AC -20 % / + 10 %
3 AC 0 V ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
FSA ... FSC
Uk ≥ 2 %, for lower values, we recommend a line reactor, or a Power Module
with the next higher power rating.
FSD ... FSF
Line reactor not required
FSA ... FSC
0.7 without line reactor for Uk ≥ 2 %
0.85 with line reactor for Uk < 2 %
FSD ... FSF
0.95 line reactor not required
< LO base load input current
The inverter insulation is designed for surge voltages according to overvoltage Category III.
4 kHz (factory setting),
Adjustable as follows in 2 kHz steps:
• 4 kHz ... 16 kHz for devices from 0.55 kW ... 30 kW.
• 4 kHz ... 8 kHz for devices 36 kW and higher
If you increase the pulse frequency, the inverter reduces the maximum output current.
10.2 Technical data, Power Modules
for LO base load power 0.55 kW ... 4 kW
for HO base load power 0.37 kW ... 3 kW
for LO base load power 0.55 kW ... 7.5 kW
for HO base load power 0.37 kW ... 5.5 kW
Technical data
433