Technical data
12.1
Technical data for CU230P-2
Feature
Order numbers
Operating voltage
Current consumption
Power loss
Output voltages
Setpoint resolution
Digital inputs
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
Data / explanation
6SL3243-0BB30-1CA3
6SL3243-0BB30-1HA3
6SL3243-6BB30-1HA3
6SL3243-0BB30-1PA3
6SL3243-0BB30-1FA0
You have two options for the Control Unit power supply:
Supply from the Power Module
•
External supply via terminals 31 and 32 with 20.4 ... 28.8 VDC.
•
Use a power supply with (PELV = Protective Extra Low Voltage according to
EN 61800-5-1), Class 2.
The 0 V of the power supply must be connected low-resistant with the PE of the system.
Max 0.5 A
The current consumption can be higher if the Control Unit supplies external components.
5.0 W
+24 V out (terminal 9), 18 V ... 28.8 V, max. 100 mA
+10 V out (terminals 1 and 35), 9.5 V ... 10.5 V, max. 10 mA
0.01 Hz
6 (DI 0 ... DI 5)
With CANopen interface
With RS485 interface for the following protocols:
USS
•
Modbus RTU
•
BACnet MS/TP
•
P1
•
With PROFIBUS interface.
With PROFINET interface.
Low < 5V, high > 11V
•
Electrically isolated
•
30 V maximum input voltage
•
5.5 mA current consumption
•
SIMATIC-compatible
•
PNP/NPN switchable
•
10 ms response time for debounce time p0724 = 0.
•