6.13 List of alarms and faults

6.13
List of alarms and faults
Syntax for faults and alarms
F12345
A67890
C01700
The table in this manual only contains the alarms and faults of the safety functions. The
complete list of all alarms and faults of the inverter, detailed causes and remedial measures
can be found in the List Manual.
Signal
Cause
Complete information on the messages is available in the List Manual.
F01600
STOP A initiated.
F01611
Defect in a monitoring channel.
More detailed information is provided
by fault value r0949.
242
Fault 12345
Alarm 67890
Message 1700 for safety functions
These messages are either alarms or faults, see the following table.
Remedy
1. Select STO and then deselect again.
2. If it cannot be acknowledged, replace the Control Unit.
The complete list of the fault values is provided in the List Manual.
0: Stop request from processor 2.
1 ... 999: Fault in data cross-check between processor 1 and
processor 2.
Details and remedy: Please refer to the List Manual.
1000: Check (watchdog) timer has expired.
When selecting a safety function, the signal changed too frequently.
The inverter monitors the signal to select a safety function after a
signal change.
If the signal state continues to change in shorter intervals than
entered in p9650, after the time 5 × p9650 the inverter outputs fault
F1611:
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA