Alarms, faults and system messages

9.5 List of alarms and faults

9.5
List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 9- 7
The most important alarms and faults of the safety functions
Number
Cause
F01600
STOP A Triggered
F01650
Acceptance test required
F01659
Write task for parameter rejected Cause: The converter should be reset to the factory setting. The resetting of
A01666
Static 1 signal atF-DI for safe
acknowledgment
A01698
Commissioning mode active for
safety functions
A01699
Shutdown path test required
F30600
STOP A Triggered
416
Remedy
STO Select and then deselect again.
Carry out acceptance test and create test certificate.
Switch the Control Unit off and then on again.
the safety functions is, however, not allowed, because the safety functions
are currently enabled.
Remedy with operator panel:
p0010 = 30
Parameter reset
p9761 = ...
Enter password for the safety functions.
p0970 = 5
Reset Start Safety Parameter.
The converter sets p0970 = 5 if it has reset the parameters.
Then reset the converter to the factory setting again.
F-DI to a logical 0 signal.
This message is withdrawn after the Safety commissioning has ended.
After the next time that the "STO" function is deselected, the message is
withdrawn and the monitoring time is reset.
STO Select and then deselect again.
Operating Instructions, 01/2016, FW V4.7 SP6, A5E31759476B AE
Converter with CU250S-2 Control Unit