Troubleshooting And Additional Information; List Of Alarms And Faults - Siemens SINAMICS G120C Compact Operating Instructions

Low-voltage inverters built-in devices, frame sizes d...f
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Troubleshooting and additional information

5.1

List of alarms and faults

Axxxxx Alarm
Fyyyyy: Fault
Table 5- 1
The most important alarms and faults
Number
Cause
F01000
Internal software error
F01001
FloatingPoint exception
F01015
Internal software error
F01018
Power-up aborted more than
once
A01028
Configuration error
F01033
Unit switchover: Reference pa-
rameter value invalid
F01034
Unit switchover: Calculation of
the parameter values after refer-
ence value change unsuccessful
F01040
Parameters must be saved
F01044
Loading memory data card de-
fective
F01105
CU: Insufficient memory
F01122
Frequency at the probe input too
high
F01205
CU: Time slice overflow
F01250
CU hardware fault
F01512
An attempt has been made to
establish a conversion factor for
scaling which does not exist
A01590
Motor maintenance interval
elapsed
F01600
STOP A initiated
F01650
Acceptance test required
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
Remedy
Replace the inverter.
Switch off the inverter and switch on again
Upgrade firmware or contact technical support.
1. Switch off the inverter power supply and switch it on again.
2. After this fault, the inverter powers up with the factory settings.
3. Recommission the inverter.
Explanation: The parameter assignments on the memory card were made
with a different type of module (article no.).
Check the module parameters and recommission if necessary.
Set the value of the reference parameter to a value other than 0.0 (p0304,
p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters involved
can be calculated in the per unit notation (p0304, p0305, p0310, p0596,
p2000, p2001, p2002, p2003, r2004).
Backup parameter (p0971).
Switch off the inverter and switch on again.
Replace the memory card or the inverter.
Reduce number of data sets.
Reduce the frequency of the pulses at the probe input.
Contact technical support.
Replace the inverter.
Create scaling or check transfer value.
Carry out the maintenance.
Select STO and then deselect again.
Carry out an acceptance test and create test certificate.
Switch off the Control Unit and switch on again.
5
79