ABB RELION REX640 Technical Manual page 1147

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
SRCPTOC Input signals
Table 1088: SRCPTOC Input signals
Name
I3P
BLOCK
RESO_IN
SRCPTOC Output signals
Table 1089: SRCPTOC Output signals
Name
ALARM
OPERATE
4.12.4.8
SRCPTOC Settings
Table 1090: SRCPTOC Group settings (Basic)
Parameter
Values (Range)
Alarm start value
0.03...0.50
Start value
0.03...0.50
Tuning harmonic
1...11
Num
Operate delay time
120...360000
Alarm delay time
120...360000
Table 1091: SRCPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
REX640
Technical Manual
Type
SIGNAL
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
xIn
0.01
xIn
0.01
1
ms
1
ms
1
Unit
Step
Protection functions
Default
Description
-
Three-phase currents
0=False
Block signal for acti-
vating the blocking
mode
0=False
Input signal from
higher frequency res-
onance branch
Description
Alarm
Operate signal
Default
0.03
0.03
11
200
200
Default
1=on
Description
Alarm limit for fil-
tered harmonic cur-
rents
Tripping limit for
filtered harmonic
currents indicating
resonance condi-
tion
Tuning frequency
harmonic number
of the filter branch
Operate delay time
for resonance
Alarm delay time
for resonance
alarm
Description
Operation Off / On
1147