ABB RELION REX640 Technical Manual page 1026

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Characteristic
Reset ratio
Retardation time
Operate time accuracy
Suppression of harmonics
4.7.3.11
Technical revision history
Table 957: UEXPDIS Technical revision history
Product
connectivi
ty level
PCL4
4.7.4
Three-phase underimpedance protection UZPDIS (ANSI
21G)
4.7.4.1
Identification
Function description
Three-phase underimpedance pro-
tection
4.7.4.2
Function block
Figure 569: Function block
4.7.4.3
Functionality
The three-phase underimpedance protection UZPDIS is generally applied as a
backup protection for generators and transformers against short circuit faults.
The protection is based on the origin-centric circular characteristics on the
impedance plane. The function calculates the impedance value from the voltage
and current phasors. If the impedance vector enters the origin-centric circle, the
function produces the operating signal after a set delay. The operating time
characteristics are according to definite time (DT).
However, it is also possible to enable separate zones of offset-mho based
protection with multiple instances of the function.
1026
Technical
Change
revision
C
Added support for settable blinder in offset mho characteristic.
Value
Typically 1.04
Total retardation time when the impedance
returns from the operating circle <40 ms
±1.0% of the set value or ±20 ms
-50 dB at f = n × f
IEC 61850
IEC 60617
identification
identification
UZPDIS
Z<G
1MRS759142 F
, where n = 2, 3, 4, 5,...
n
ANSI/IEEE C37.2
device number
21G
REX640
Technical Manual