ABB RELION REX640 Technical Manual page 656

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
I
L mLV
2
I
L mLV
3
The "Y" side currents stay untouched, while the "d" side currents are compensated
to match the currents actually flowing in the windings.
In this example there is no neutral current on either side of the transformer
(assuming there are no earthing transformers installed). In the previous example,
the matching is done differently to have the winding 1 neutral current compensated
at the same time.
Table 646: LNPLDF vector group matching
Vector group of
the transformer
Table continues on the next page
656
I
I
L
2
L
1
=
3
I
I
L
3
L
2
=
3
Winding 1 type
Yy0
Y
YNy0
YN
YNyn0
YN
Yyn0
Y
Yy2
Y
YNy2
YN
YNyn2
YN
Yyn2
Y
Yy4
Y
YNy4
YN
YNyn4
YN
Yyn4
Y
Yy6
Y
YNy6
YN
YNyn6
YN
Yyn6
Y
Yy8
Y
YNy8
YN
YNyn8
YN
Yyn8
Y
Yy10
Y
Winding 2 type
Phase shift
y
y
yn
yn
y
y
yn
yn
y
y
yn
yn
y
y
yn
yn
y
y
yn
yn
y
1MRS759142 F
(Equation 150)
(Equation 151)
Zero sequence
current
elimination
0
Not needed
0
HV side
0
HV & LV side
0
LV side
2
Not needed
2
(Automatic)
2
(Automatic)
2
(Automatic)
4
Not needed
4
(Automatic)
4
(Automatic)
4
(Automatic)
6
Not needed
6
HV side
6
HV & LV side
6
LV side
8
Not needed
8
(Automatic)
8
(Automatic)
8
(Automatic)
10
Not needed
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents