ABB RELION REX640 Technical Manual page 1375

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
7.1.9
SSCBR Monitored data
Table 1314: SSCBR Monitored data
Name
Type
T_TRV_OP
FLOAT32
T_TRV_CL
FLOAT32
T_SPR_CHR
FLOAT32
NO_OPR
INT32
INA_DAYS
INT32
CB_LIFE_A
INT32
CB_LIFE_B
INT32
CB_LIFE_C
INT32
IPOW_A
FLOAT32
IPOW_B
FLOAT32
IPOW_C
FLOAT32
SSCBR
Enum
7.1.10
Technical data
Table 1315: SSCBR Technical data
Characteristic
Current measuring accuracy
Operate time accuracy
Travelling time measurement
REX640
Technical Manual
Values (Range)
Unit
0...60000
ms
0...60000
ms
0.00...99.99
s
0...99999
0...9999
-99999...99999
-99999...99999
-99999...99999
0.000...30000.000
0.000...30000.000
0.000...30000.000
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
±1.5 % or ±0.002 × I
(at currents in the range of 0.1...10 × I
±5.0 %
(at currents in the range of 10...40 × I
±1.0 % of the set value or ±20 ms
+10 ms / -0 ms
Condition monitoring functions
Description
Travel time of the CB
during opening opera-
tion
Travel time of the CB
during closing opera-
tion
The charging time of
the CB spring
Number of CB opera-
tion cycle
The number of days CB
has been inactive
CB Remaining life phase
A
CB Remaining life phase
B
CB Remaining life phase
C
Accumulated currents
power (Iyt), phase A
Accumulated currents
power (Iyt), phase B
Accumulated currents
power (Iyt), phase C
Status
n
)
n
)
n
1375

Advertisement