Protection functions
4.10.2
Function block
Figure 613: Function block
4.10.3
Functionality
The motor start-up supervision function STTPMSU is designed for protection
against excessive starting time and locked rotor conditions of the motor during
starting. For a good and reliable operation of the motor, the thermal stress during
the motor starting is maintained within the allowed limits.
The starting of the motor is supervised by monitoring the TRMS magnitude of all
the phase currents or by monitoring the status of the circuit breaker connected to
the motor.
During the start-up period of the motor, STTPMSU calculates the integral of the I²t
value. If the calculated value exceeds the set value, the operate signal is activated.
STTPMSU has the provision to check the locked rotor condition of the motor using
the speed switch, which means checking if the rotor is able to rotate or not. This
feature operates after a predefined operating time.
STTPMSU also protects the motor from an excessive number of start-ups. Upon
exceeding the specified number of start-ups within certain duration, STTPMSU
blocks further starts. The restart of the motor is also inhibited after each start
and continues to be inhibited for a set duration. When the lock of start of motor is
enabled, STTPMSU gives the time remaining until the restart of the motor.
STTPMSU contains a blocking functionality. It is possible to block function outputs,
timer or the function itself.
4.10.4
Analog input configuration
STTPMSU has one analog group input which must be properly configured.
Table 1035: Analog inputs
Input
I3P
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
1094
See the preprocessing function blocks in this document for the possible
signal sources.
Description
Three-phase currents
1MRS759142 F
REX640
Technical Manual