Protection functions
to capacitor manufacturing tolerances. The natural unbalance current must be
compensated for before using the measured unbalance current for the function
operation. The natural unbalance current needs to be recorded when there is no
fault in the capacitor banks, and it is initiated through the command
unbalance , available under menu path Control > CUBPTOC. By selecting Record
unbalance with value "Record", the measured unbalance current
as the natural unbalance current
and angle of the recorded natural unbalance current I_AMPL_NAT and I_ANGL_NAT
are available in the monitored data view.
Once the natural unbalance current is recorded during further executions of the
function, the natural unbalance current is subtracted from the measured unbalance
current
Figure 630
Figure 630: Natural unbalance compensation. (a) Healthy condition when the natural
unbalance is recorded (b) Unbalance compensation during faulty conditions
The natural unbalance current compensation is enabled using the setting
Comp Enable . If Natural Comp Enable is set to "FALSE", the unbalance current is not
compensated. If
current is calculated based on the equation.
I
CompUnb
The amplitude I_AMPL_COMP and the angle I_ANGL_COMP of the compensated
unbalance current
1122
I
to obtain the compensated unbalance current
Unb
.
Natural Comp Enable is set to "TRUE", the compensated unbalance
I
I
=
Unb
NatUnb
I
are available in the monitored data view.
CompUnb
I
and is stored as a reference. The amplitude
NatUnb
1MRS759142 F
Record
I
is considered
Unb
I
as shown in
CompUnb
Natural
(Equation 286)
REX640
Technical Manual