ABB RELION REX640 Technical Manual page 1345

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
6.7.6.1
MSCPMRI Input signals
Table 1288: MSCPMRI Input signals
Name
BLOCK
START_EMERG
RESET
MOT_RUN
TEMP_RL
6.7.6.2
MSCPMRI Output signals
Table 1289: MSCPMRI Output signals
Name
OPERATE
BLK_RESTART
6.7.7
MSCPMRI Settings
Table 1290: MSCPMRI Group settings (Basic)
Parameter
Values (Range)
Warm start level
20.0...100.0
Max Num cold start 1...10
Max Num warm
1...10
start
Cnt decrease time
1...180
Table 1291: MSCPMRI Group settings (Advanced)
Parameter
Values (Range)
Cnt Dec timer Mult
1.00...10.00
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
FLOAT32
Type
BOOLEAN
BOOLEAN
Unit
Step
%
0.1
1
1
min
1
Unit
Step
0.01
Supervision functions
Default
Description
0=False
Block signal for acti-
vating the blocking
mode
0=False
Signal to indicate the
need of emergency
start
0=False
Reset cold and warm
start counter value
0=False
Signal to show that
motor start up is in
progress
0.00
Thermal level of the
motor
Description
Operate signal
Restart inhibited
Default
35.0
2
1
60
Default
1.00
Description
Thermal threshold
to define a warm
start
Maximum number
of cold start al-
lowed
Maximum number
of warm start al-
lowed
Counter decrease
time
Description
Multiplier for coun-
ter decrease timer
1345

Advertisement

Table of Contents
loading

Table of Contents