Supervision functions
6.2.8
CCSPVC Settings
Table 1248: CCSPVC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Start value
0.05...0.50
Table 1249: CCSPVC Non group settings (Advanced)
Parameter
Values (Range)
Max operate cur-
1.00...5.00
rent
6.2.9
CCSPVC Monitored data
Table 1250: CCSPVC Monitored data
Name
Type
IDIFF
FLOAT32
CCSPVC
Enum
6.2.10
Technical data
Table 1251: CCSPVC Technical data
Characteristic
Operate time (including the delay of the out-
put contact)
6.2.11
Technical revision history
Table 1252: CCSPVC Technical revision history
Product
connectivi
ty level
PCL4
1318
Unit
xIn
Unit
xIn
Values (Range)
0.00...40.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Technical
Change
revision
Start value maximum extended to 0.50xIn.
F
Setting
Step
Default
1=on
0.01
0.05
Step
Default
0.01
1.50
Unit
xIn
Value
<30 ms
1MRS759142 F
Description
Operation On / Off
Minimum operate
current differential
level
Description
Block of the func-
tion at high phase
current
Description
Differential current
Status
REX640
Technical Manual