ABB RELION REX640 Technical Manual page 1369

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
The operation of the subfunction can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 782: Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals PRES_LO_IN and
PRES_ALM_IN.
Timer 1
When the PRES_ALM_IN binary input is activated, the PRES_ALM alarm is activated
after a time delay set with the
be blocked by activating the BLOCK input.
Timer 2
If the pressure drops further to a very low level, the PRES_LO_IN binary input
becomes high, activating the lockout alarm PRES_LO after a time delay set with
the
BLOCK input.
7.1.6
Application
SSCBR includes different metering and monitoring subfunctions.
Circuit breaker status
Circuit breaker status monitors the position of the circuit breaker, that is, whether
the breaker is in an open, closed or intermediate position.
Circuit breaker operation monitoring
The purpose of the circuit breaker operation monitoring is to indicate that the
circuit breaker has not been operated for a long time. The function calculates the
number of days the circuit breaker has remained inactive, that is, has stayed in the
same open or closed state. There is also the possibility to set an initial inactive day.
Breaker contact travel time
High traveling times indicate the need for the maintenance of the circuit breaker
mechanism. Therefore, detecting excessive traveling time is needed. During the
opening cycle operation, the main contact starts opening. The auxiliary contact
A opens, the auxiliary contact B closes and the main contact reaches its opening
position. During the closing cycle, the first main contact starts closing. The auxiliary
contact B opens, the auxiliary contact A closes and the main contact reaches its
REX640
Technical Manual
Pres lockout time setting. The PRES_LO alarm can be blocked by activating the
Pressure alarm time setting. The PRES_ALM alarm can
Condition monitoring functions
1369