ABB RELION REX640 Technical Manual page 1108

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
The temperature protection using the RTD sensors can be done using the function
block. The measured temperature can be fed from the RTD sensor to the function
input that detects too high temperatures in the motor bearings or windings, for
example. When the ENA_ADD input is enabled, the threshold value of the internal
comparator is the sum of the
temporal increase or decrease of the level detector depending on the sign and value
of the
If, for example,
active, the input signal needs to rise above 120 before MAPGAPC operates.
4.11.6
Signals
4.11.6.1
MAPGAPC Input signals
Table 1046: MAPGAPC Input signals
Name
AI_VALUE
BLOCK
ENA_ADD
4.11.6.2
MAPGAPC Output signals
Table 1047: MAPGAPC Output signals
Name
OPERATE
START
4.11.7
MAPGAPC Settings
Table 1048: MAPGAPC Group settings (Basic)
Parameter
Values (Range)
Start value
-10000.0...10000.0
Start value Add
-100.0...100.0
Operate delay time
0...200000
Table 1049: MAPGAPC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Operation mode
1=Over
2=Under
1108
Start value Add setting, for example, when the emergency start is activated.
Start value is 100, Start value Add is 20 and the ENA_ADD input is
Type
FLOAT32
BOOLEAN
BOOLEAN
Unit
ms
Unit
Start value Add and Start value settings. This allows a
Default
0.0
0=False
0=False
Type
BOOLEAN
BOOLEAN
Step
0.1
0.1
100
Step
1MRS759142 F
Description
Analogue input value
Block signal for acti-
vating the blocking
mode
Enable start added
Description
Operate
Start
Default
Description
0.0
Start value
0.0
Start value Add
0
Operate delay time
Default
Description
1=on
Operation Off / On
1=Over
Operation mode
Technical Manual
REX640