ABB RELION REX640 Technical Manual page 1285

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
Max forward angle
0...90
Max reverse angle
0...90
Min forward angle
0...90
Min reverse angle
0...90
Directional mode
1=Non-directional
2=Forward
3=Reverse
Table 1216: DPSRDIR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 1217: DPSRDIR Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Min operate current 0.01...1.00
Min operate volt-
0.01...1.00
age
5.14.9
DPSRDIR Monitored data
Table 1218: DPSRDIR Monitored data
Name
Type
ANGLE_RCA
FLOAT32
DPSRDIR
Enum
5.15
Neutral power directional element DNZSRDIR (ANSI
67N-TC)
REX640
Technical Manual
Unit
Step
deg
1
deg
1
deg
1
deg
1
Unit
Step
Unit
Step
ms
1
xIn
0.01
xUn
0.01
Values (Range)
-180.00...180.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection related functions
Default
88
88
88
88
2=Forward
Default
1=on
Default
20
0.10
0.30
Unit
Description
deg
Angle between operat-
ing angle and charac-
teristic angle
Status
Description
Maximum phase
angle in forward di-
rection
Maximum phase
angle in reverse di-
rection
Minimum phase an-
gle in forward di-
rection
Minimum phase an-
gle in reverse direc-
tion
Directional mode
Description
Operation Off / On
Description
Reset delay time
Minimum operating
current
Minimum operating
voltage
1285