ABB RELION REX640 Technical Manual page 1092

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.9.7.1
ARCSARC Input signals
Table 1029: ARCSARC Input signals
Name
I3P
IRES
BLOCK
REM_FLT_ARC
OPR_MODE
4.9.7.2
ARCSARC Output signals
Table 1030: ARCSARC Output signals
Name
OPERATE
ARC_FLT_DET
ALARM
4.9.8
ARCSARC Settings
Table 1031: ARCSARC Group settings (Basic)
Parameter
Values (Range)
Phase start value
0.50...40.00
Ground start value
0.05...8.00
Operation mode
1=Light+current
2=Light only
3=BI controlled
Table 1032: ARCSARC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Sensor supervision 0=off
1=on
1092
Type
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
xIn
0.01
xIn
0.01
Unit
Step
Default
Description
-
Three-phase currents
-
Residual current
0=False
Block signal for all bi-
nary outputs
0=False
Remote Fault arc de-
tected
0=False
Operation mode in-
put
Description
Operate
Fault arc detected=light sig-
nal output
Self supervision alarm
Default
2.50
0.20
1=Light+current
Default
1=on
1=on
1MRS759142 F
Description
Operating phase
current
Operating residual
current
Operation mode
Description
Operation Off / On
Sensor supervision
selection
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents